INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS



                  805.4.2.2  Heat release rate. Newly introduced mat-  806.2 Obstruction of means of egress. The required width
                  tresses shall have limited  rates  of heat  release  when  of any portion of a means of egress shall not be obstructed by
                  tested in accordance with ASTM E1590 or California  decorative vegetation. Natural cut trees shall not be located
                  Technical Bulletin 129, as follows:             within an exit, corridor, or a lobby or vestibule.
                    1. The peak rate of heat release for the single mat-  806.3 Open flame. Candles and open flames shall not be
                       tress shall not exceed 100 kW.             used on or near decorative vegetation. Natural cut trees shall
                         Exception: Mattresses in rooms or spaces  be kept a distance from heat  vents and  any  open flame or
                         protected by an approved automatic sprinkler  heat-producing devices not less than the height of the tree.
                         system  installed  in accordance with Section  806.4 Electrical fixtures and wiring. The use of unlisted
                         903.3.1.1.                               electrical wiring and lighting on natural vegetation, including
                    2. The total heat  released by the  single mattress  natural cut trees, shall be prohibited.
                       during the first 10 minutes of the test  shall not
                       exceed 25 MJ.
                                                                                    SECTION 807
                         Exception: Mattresses in rooms or spaces           DECORATIVE MATERIALS AND
                         protected by an approved automatic sprinkler   ARTIFICIAL DECORATIVE VEGETATION
                         system  installed  in accordance with Section    IN NEW AND EXISTING BUILDINGS
                         903.3.1.1.
                                                                  807.1 General. The following requirements shall apply to all
                  805.4.2.3 Identification. Mattresses shall bear the label  occupancies:
                  of an  approved agency, confirming compliance with
                  the requirements of Sections 805.4.2.1 and 805.4.2.2.  1. Furnishings or decorative materials of an explosive or
                                                                       highly flammable character shall not be used.
                                                                     2. Fire-retardant coatings in existing buildings shall be
                               SECTION 806                             maintained so as to retain the effectiveness of the treat-
                   NATURAL DECORATIVE VEGETATION                       ment under service conditions  encountered in actual
                     IN NEW AND EXISTING BUILDINGS                     use.
             806.1 Natural cut trees. Natural cut trees, where allowed by  3. Furnishings  or other  objects shall not be placed to
             this section, shall have the trunk bottoms cut off not less than  obstruct exits, access thereto, egress therefrom or visi-
             0.5 inch (12.7 mm) above the original cut and shall be placed  bility thereof.
             in a support device complying with Section 806.1.2.     4. The permissible amount of noncombustible decorative
               806.1.1 Restricted occupancies. Natural cut trees shall be  materials shall not be limited.
               prohibited within ambulatory care facilities and Group A,  807.2 Combustible decorative materials. In Groups A, B, E,
               E, I-1, I-2, I-3, I-4, M, R-1, R-2 and R-4 occupancies.  I, M and R-1 and in dormitories in Group R-2, curtains, drap-
                  Exceptions:                                     eries, fabric hangings and other similar combustible decora-
                    1. Trees located in areas protected by an approved  tive materials suspended from walls or ceilings shall comply
                       automatic sprinkler  system installed in accor-  with Section 807.3 and shall not exceed 10 percent of the spe-
                       dance with Section 903.3.1.1 or 903.3.1.2 shall  cific wall or ceiling area to which such materials are attached.
                       not be prohibited in Groups A, E, M, R-1 and  Fixed or movable walls and partitions, paneling, wall pads
                       R-2.                                       and crash pads applied structurally or for decoration, acousti-
                    2. Trees shall be allowed within  dwelling units in  cal correction, surface insulation or other purposes shall be
                       Group R-2 occupancies.                     considered to  be  interior finish, shall comply with  Section
                                                                  803 and shall not be considered decorative materials or fur-
               806.1.2 Support devices. The support device that holds  nishings.
               the tree in an upright position shall be of a type that is sta-
               ble and that meets all of the following criteria:     Exceptions:
                  1. The device shall hold the tree securely and be of  1. In auditoriums in Group A, the permissible amount
                    adequate size to avoid tipping over of the tree.     of  curtains,  draperies, fabric hangings and similar
                                                                         combustible decorative material  suspended from
                  2. The device shall  be  capable of containing a mini-  walls or ceilings shall not exceed 75 percent of the
                    mum two-day supply of water.
                                                                         aggregate wall area where the building is equipped
                  3. The water level, when full, shall cover the tree stem  throughout with an  approved automatic sprinkler
                    not less than 2 inches (51 mm). The water level shall  system  in accordance with Section 903.3.1.1, and
                    be maintained above the fresh cut and checked not    where the material is installed in accordance with
                    less than once daily.                                Section 803.15 of the International Building Code.
               806.1.3 Dryness. The tree  shall be removed  from the   2. In Group R-2 dormitories, within sleeping units and
               building whenever the needles or leaves fall off readily  dwelling units, the permissible amount of curtains,
               when a tree branch is shaken or if the needles are brittle  draperies,  fabric hangings and similar decorative
               and break when bent between the thumb and index finger.   materials suspended from walls or ceilings shall not
               The tree shall be checked daily for dryness.
         *