INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
807.5.3.1 Group I-1 and I-2 Condition 1 within not more than 50 percent of the specific wall area to
units. In Group I-1 and Group I-2 Condition 1 occu- which they are attached.
pancies, equipped throughout with an approved auto- 807.5.6 Dormitories in Group R-2. In Group R-2 dormi-
matic sprinkler system installed in accordance with tories, within sleeping units and dwelling units, the com-
Section 903.3.1.1, within sleeping units and dwelling bustible decorative materials shall be of limited quantities
units, combustible decorative materials placed on walls such that a hazard of fire development or spread is not
shall be limited to not more than 50 percent of the wall present.
area to which they are attached.
807.5.3.2 In Group I-1 and I-2, Condition 1 for areas
other than within units. In Group I-1 and Group I-2, SECTION 808
Condition 1 occupancies, equipped throughout with an FURNISHINGS OTHER THAN UPHOLSTERED
approved automatic sprinkler system installed in accor- FURNITURE AND MATTRESSES OR DECORATIVE
dance with Section 903.3.1.1, combustible decorative MATERIALS IN NEW AND EXISTING BUILDINGS
materials placed on walls in areas other than within 808.1 Wastebaskets and linen containers in Group I-1, I-2
dwelling and sleeping units shall be limited to not more and I-3 occupancies and Group B ambulatory care facili-
than 30 percent of the wall area to which they are ties. Wastebaskets, linen containers and other waste contain-
attached. ers, including their lids, located in Group I-1, I-2 and I-3
807.5.3.3 In Group I-2, Condition 2. In Group I-2, occupancies and Group B ambulatory care facilities shall be
Condition 2 occupancies, equipped throughout with an constructed of noncombustible materials or of materials that
approved automatic sprinkler system installed in accor- meet a peak rate of heat release not exceeding 300 kW/m 2
dance with Section 903.3.1.1, combustible decorative when tested in accordance with ASTM E1354 at an incident
2
materials placed on walls shall be limited to not more heat flux of 50 kW/m in the horizontal orientation. Metal
than 30 percent of the wall area to which they are wastebaskets and other metal waste containers with a capac-
attached. ity of 20 gallons (75.7 L) or more shall be listed in accor-
dance with UL 1315 and shall be provided with a
807.5.3.4 Other areas in Groups I-1 and I-2. In
Group I-1 and I-2 occupancies, in areas not equipped noncombustible lid. Portable containers exceeding 32 gallons
throughout with an approved automatic sprinkler sys- (121 L) shall be stored in an area classified as a waste and
tem, combustible decorative materials shall be of such linen collection room and constructed in accordance with
limited quantities that a hazard of fire development or Table 509 of the International Building Code.
spread is not present. Exception: Recycling containers complying with Section
808.1.2 are not required to be stored in waste and linen
807.5.4 Group I-3. In Group I-3, combustible decorative
materials are prohibited. collection rooms.
808.1.1 Capacity density. The average capacity density
807.5.5 Group I-4. Group I-4 occupancies shall comply
with the requirements in Sections 807.5.5.1 through of containers located in an individual room or space, other
807.5.5.3. than waste and linen collection rooms, shall not be greater
2
2
than 0.5 gal/ft (20.4 L/m ).
807.5.5.1 Storage in corridors and lobbies. Clothing
and personal effects shall not be stored in corridors and 808.1.2 Recycling clean waste containers. Recycling
clean waste containers, including their lids, shall not
lobbies.
exceed an individual capacity of 96 gallons (363 L).
Exceptions:
808.2 Waste containers with a capacity of 20 gallons or
1. Corridors protected by an approved automatic more in Group R-2 college and university dormitories.
sprinkler system installed in accordance with Waste containers, including their lids, located in Group R-2
Section 903.3.1.1.
college and university dormitories, and with a capacity of 20
2. Corridors protected by an approved fire alarm gallons (75.7 L) or more, shall be constructed of noncombus-
system installed in accordance with Section tible materials or of materials that meet a peak rate of heat
2
907. release not exceeding 300 kW/m when tested in accordance
2
3. Storage in metal lockers, provided the mini- with ASTM E1354 at an incident heat flux of 50 kW/m in
mum required egress width is maintained. the horizontal orientation. Metal wastebaskets and other
metal waste containers with a capacity of 20 gallons (75.7 L)
807.5.5.2 Artwork in corridors. Artwork and teaching
materials shall be limited on walls of corridors to not or more shall be listed in accordance with UL 1315 and shall
be provided with a noncombustible lid. Portable containers
more than 20 percent of the wall area.
exceeding 32 gallons (121 L) shall be stored in an area classi-
807.5.5.3 Artwork in classrooms. Artwork and teach- fied as a waste and linen collection room constructed in
ing materials shall be limited on walls of classrooms to
accordance with Table 509 of the International Building
Code.