Page 129 - 2018_IFC
P. 129

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS



         804.2 Foam plastic interior trim. Foam plastic used as inte-  materials in  enclosures for  stairways and  ramps,  exit
         rior trim shall comply with Sections 804.2.1 through 804.2.4.  passageways, corridors and rooms or spaces not sepa-
           804.2.1 Density. The minimum density of the interior trim  rated from corridors by full-height partitions extending
                                               3
           shall be 20 pounds per cubic foot (320 kg/m ).          from the floor to the underside of the ceiling shall with-
                                                                   stand a  minimum  critical radiant flux.  The minimum
           804.2.2 Thickness. The maximum thickness of the inte-   critical radiant  flux shall be not less than Class I in
                           1
           rior  trim shall be  /   inch (12.7 mm) and the maximum  Groups I-1,  I-2 and I-3 and not less than Class  II in
                            2
           width shall be 8 inches (203 mm).
                                                                   Groups A, B, E, H, I-4, M, R-1, R-2 and S.
           804.2.3 Area limitation. The interior trim shall not consti-  Exception: Where a building is equipped through-
           tute more than 10 percent of the specific wall or ceiling  out with an  automatic sprinkler system in accor-
           area to which it is attached.
                                                                     dance with Section 903.3.1.1 or 903.3.1.2, Class II
           804.2.4 Flame spread. The flame spread index shall not    materials shall be permitted in any area where Class
           exceed 75 where tested in accordance with ASTM E84 or     I materials  are required and materials complying
           UL 723. The smoke-developed index shall not be limited.   with DOC  FF-1 “pill test” (CPSC 16 CFR Part
              Exception: Where the interior trim material has been   1630) or with ASTM D2859 shall be permitted in
              tested  as an interior finish in accordance with NFPA  any area where Class II materials are required.
              286 and complies with the acceptance criteria in Sec-  804.4 Interior floor-wall base. Interior floor-wall base that
              tion 803.1.1.1, it is not required to be tested for flame  is 6 inches (152 mm) or less in height shall  be tested in
              spread index in accordance with  ASTM E84  or UL  accordance with ASTM E648 or NFPA 253 and shall be not
              723.                                            less than Class II. Where a Class I floor finish is required,
         804.3 New interior floor finish.  New interior floor finish  the  floor-wall base  shall be Class I. The classification
         and floor covering materials in new and existing buildings  referred  to  herein corresponds to the classifications  deter-
         shall comply with Sections 804.3.1 through 804.3.3.2.   mined  by  ASTM E648  or NFPA 253 as follows: Class I,
                                                                         2
                                                                                                      2
                                                              0.45 watt/cm  or greater; Class II, 0.22 watts/cm  or greater.
           Exception: Floor finishes and coverings of a traditional
           type, such as wood, vinyl, linoleum or terrazzo, and resil-  Exception: Interior trim materials that comply with Sec-
           ient floor covering materials that are not  composed of  tion 804.1.
           fibers.
           804.3.1 Classification. Interior floor finish and floor cov-         SECTION 805
           ering materials required by Section  804.3.3.2 to be of     UPHOLSTERED FURNITURE AND
           Class I or II  materials  shall be classified  in accordance  MATTRESSES IN NEW AND EXISTING BUILDINGS
           with  ASTM  E648 or NFPA 253. The classification
           referred to herein corresponds to the classifications deter-  805.1 Group I-1, Condition 2. The requirements in Sections
           mined by ASTM E648 or NFPA 253 as follows: Class I,  805.1.1 through 805.1.2 shall apply to facilities in Group I-1,
                       2
                                                       2
           0.45 watts/cm  or greater; Class II, 0.22  watts/cm  or  Condition 2.
           greater.                                              805.1.1 Upholstered furniture. Newly introduced uphol-
           804.3.2  Testing and identification.  Interior floor finish  stered furniture shall meet  the requirements of Sections
           and  floor covering materials shall be  tested by an  805.1.1.1 through 805.1.1.3.
           approved agency in accordance with ASTM E648 or         805.1.1.1 Ignition by cigarettes. Newly  introduced
           NFPA 253 and identified by a hang tag or other suitable  upholstered furniture shall be shown to resist ignition
           method so as to identify the manufacturer or supplier and  by cigarettes as determined by tests conducted in accor-
           style, and  shall indicate the  interior floor  finish  or floor  dance with one of the following:
           covering classification  in accordance with  Section      1. Mocked-up composites of the upholstered furni-
           804.3.1. Carpet-type floor coverings shall be tested as pro-  ture shall have a char length not exceeding 1.5
           posed for use, including underlayment. Test reports con-     inches (38 mm) when tested in accordance with
           firming  the information provided in  the  manufacturer’s    NFPA 261.
           product identification shall be furnished to the fire code
           official upon request.                                    2. The  components  of the upholstered furniture
                                                                        shall meet the requirements for Class I when
           804.3.3 Interior floor finish requirements. New interior     tested in accordance with NFPA 260.
           floor  coverings materials shall  comply with  Sections
           804.3.3.1 and 804.3.3.2, and interior floor finish materials  805.1.1.2 Heat release rate. Newly introduced uphol-
           shall comply with Section 804.3.1.                      stered furniture shall have limited rates of heat release
                                                                   when tested in accordance with ASTM E1537 or Cali-
              804.3.3.1 Pill test. In all occupancies, new floor cover-  fornia Technical Bulletin 133, as follows:
              ing materials shall comply with the requirements of the
              DOC FF-1 “pill test” (CPSC 16 CFR Part 1630) or of     1. The peak rate of heat release for the single uphol-
              ASTM D2859.                                               stered furniture item shall not exceed 80 kW.
                                                                          Exception: Upholstered furniture in rooms or
              804.3.3.2 Minimum critical radiant flux. In all occu-
              pancies, new  interior  floor finish and floor  covering    spaces  protected by an  approved  automatic



         96                                                                         2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   124   125   126   127   128   129   130   131   132   133   134