FIRE PROTECTION AND LIFE SAFETY SYSTEMS



                  kPa) charging pressure systems. For Halon 1211 hand-  904.11.2.2 Alarms. Alarms shall  be provided as
                  hose line systems, hoses shall be tested at 2,500 psi (17  required for automatic sprinkler systems in accordance
                  238 kPa) for high-pressure systems and 900 psi (6206  with Section 903.4.2.
                  kPa) for low-pressure systems.                       904.11.2.3 Floor control valves. Floor control valves
               904.9.4 Auxiliary equipment. Auxiliary and supplemen-   shall be  provided as required  for  automatic sprinkler
               tary components, such as switches,  door  and  window   systems in accordance with Section 903.4.3.
               releases, interconnected valves, damper releases and sup-  904.11.3 Testing and maintenance. Automatic water mist
               plementary alarms, shall be manually operated  at 12-  systems shall be tested and maintained in accordance with
               month intervals to ensure such components are in proper  Section 901.6.
               operating condition.
                                                                  904.12 Commercial  cooking systems.  The automatic fire-
             904.10 Clean-agent systems. Clean-agent fire-extinguishing  extinguishing system for commercial cooking systems shall
             systems shall be installed, maintained, periodically inspected  be of a type recognized for protection of commercial cooking
             and tested in accordance with NFPA 2001 and their listing.  equipment and exhaust systems of the type and arrangement
             Records of inspections and testing shall be maintained.  protected. Preengineered automatic dry- and  wet-chemical
               904.10.1 System test. Systems shall  be inspected and  extinguishing systems shall be tested in accordance with UL
               tested for proper operation at 12-month intervals.  300 and listed and labeled for the intended application. Other
               904.10.2 Containers. The extinguishing  agent  quantity  types of automatic fire-extinguishing systems shall be listed
               and pressure of  the  containers shall be checked at  six-  and  labeled for specific use as protection for commercial
               month intervals. Where a container shows a loss in origi-  cooking operations. The system shall be installed in accor-
               nal weight  of  more than 5 percent or  a loss  in  original  dance with this code, NFPA 96, its listing and the manufac-
               pressure, adjusted for temperature, of more than 10 per-  turer’s installation instructions. Automatic fire-extinguishing
               cent, the container shall be refilled or replaced. The weight  systems of the following types shall  be installed in accor-
               and pressure of the container shall be recorded on a tag  dance with the referenced standard indicated, as follows:
               attached to the container.                            1. Carbon dioxide extinguishing systems, NFPA 12.
               904.10.3 System hoses. System hoses shall be examined  2. Automatic sprinkler systems, NFPA 13.
               at 12-month intervals for damage. Damaged hoses shall be  3. Automatic water mist systems, NFPA 750.
               replaced or  tested. All hoses  shall  be  tested at five-year
               intervals.                                            4. Foam-water sprinkler system or foam-water spray sys-
                                                                       tems, NFPA 16.
             904.11 Automatic water mist systems.  Automatic water
             mist systems shall be permitted in applications that are consis-  5. Dry-chemical extinguishing systems, NFPA 17.
             tent with the applicable listing or approvals and shall comply  6. Wet-chemical extinguishing systems, NFPA 17A.
             with Sections 904.11.1 through 904.11.3.                Exception: Factory-built commercial cooking recirculat-
               904.11.1 Design and installation requirements.  Auto-  ing systems that are tested in accordance with UL 710B
               matic water mist systems shall be designed and installed in  and listed, labeled and installed in accordance with Sec-
               accordance with Sections 904.11.1.1 through 904.11.1.4.  tion 304.1 of the International Mechanical Code.
                  904.11.1.1 General.  Automatic  water mist systems  904.12.1 Manual system operation. A manual actuation
                  shall be designed and installed in accordance  with  device shall be located at or near a means of egress from
                  NFPA 750 and the manufacturer’s instructions.      the cooking area not less than 10 feet (3048 mm) and not
                                                                     more  than  20  feet (6096 mm) from the kitchen exhaust
                  904.11.1.2 Actuation.  Automatic water mist systems
                  shall be automatically actuated.                   system. The manual actuation device shall be installed not
                                                                     more than 48 inches (1200 mm) nor less than 42 inches
                  904.11.1.3 Water supply protection. Connections to a  (1067 mm) above the floor and shall clearly identify the
                  potable water supply shall be protected against back-  hazard protected. The manual actuation shall require a
                  flow in  accordance with the  International Plumbing  maximum force of 40 pounds (178  N) and a maximum
                  Code.                                              movement of 14 inches (356 mm) to actuate the fire sup-
                  904.11.1.4 Secondary water supply. Where a second-  pression system.
                  ary water supply is required for an automatic sprinkler
                                                                       Exception:  Automatic sprinkler  systems shall not be
                  system, an automatic water  mist system shall be  pro-  required to be equipped with manual actuation means.
                  vided with an approved secondary water supply.
                                                                     904.12.2 System interconnection. The actuation of the
               904.11.2 Water mist system supervision and alarms.
                                                                     fire extinguishing system shall  automatically shut down
               Supervision and alarms shall be provided as required for  the fuel or electrical power supply to the cooking equip-
               automatic sprinkler systems in accordance with  Section  ment. The fuel and electrical supply reset shall be manual.
               903.4.
                                                                     904.12.3 Carbon dioxide systems. Where carbon dioxide
                  904.11.2.1 Monitoring. Monitoring shall be provided  systems are used, there shall be a nozzle at the top of the
                  as required for  automatic sprinkler systems in  accor-  ventilating duct. Additional nozzles that are symmetrically
                  dance with Section 903.4.1.
                                                                     arranged to give uniform distribution shall  be installed