FIRE PROTECTION AND LIFE SAFETY SYSTEMS



           containing high-piled combustible storage equipped    minimum rate of two air changes per hour based on the
           throughout with an automatic sprinkler system in accor-  volume of the building or portion thereof without contents.
           dance with Section 903.3.1.1, a smoke and heat removal  The capacity of each exhaust fan shall not exceed 30,000
                                                                                        3
           system shall be installed in accordance with Section 910.3  cubic feet per minute (14.2 m /s).
           or  910.4. In occupied portions  of  a building  equipped  910.4.3.1 Makeup air. Makeup air openings shall be
           throughout with an automatic sprinkler system in accor-  provided within 6 feet (1829 mm) of the floor level.
           dance with Section 903.3.1.1 where the upper surface of  Operation of makeup air openings shall be manual or
           the story is not a roof assembly, a mechanical smoke    automatic. The minimum  gross area  of makeup  air
           removal system in accordance with Section 910.4 shall be  inlets shall be 8 square feet  per 1,000 cubic  feet per
           installed.                                                          2           3
                                                                   minute (0.74 m  per 0.4719 m /s) of smoke exhaust.
         910.3 Smoke and heat vents. The design and installation of  910.4.4 Activation. The mechanical smoke removal sys-
         smoke and heat vents shall be in accordance with Sections  tem shall be activated by manual controls only.
         910.3.1 through 910.3.3.
                                                                 910.4.5 Manual control location. Manual controls shall
           910.3.1 Listing and labeling. Smoke and heat vents shall  be located where they are able to be accessed by the fire
           be listed and labeled to indicate compliance with UL 793
                                                                 service from an exterior door of the building and separated
           or FM 4430.
                                                                 from the remainder of the building by not less than 1-hour
           910.3.2 Smoke and heat vent locations. Smoke and heat  fire barriers constructed in accordance with Section 707
           vents shall be located 20 feet (6096 mm) or more from  of the International Building Code or horizontal assem-
           adjacent lot lines and fire walls and 10 feet (3048 mm) or  blies  constructed in accordance with Section 711  of the
           more from fire barriers. Vents shall be uniformly located  International Building Code, or both.
           within the roof in the areas of the building where the vents  910.4.6 Control wiring. Wiring for operation and control
           are required to be installed by Section 910.2, with consid-  of mechanical smoke removal systems shall be connected
           eration given to roof pitch, sprinkler location and struc-  ahead of the main disconnect in accordance with Section
           tural members.
                                                                 701.12E of NFPA 70 and be protected against interior fire
           910.3.3 Smoke and heat vents area. The required aggre-  exposure to temperatures in excess of 1,000°F (538°C) for
           gate area of smoke and heat vents shall be calculated as  a period of not less than 15 minutes.
           follows:
                                                                 910.4.7 Controls.  Where building air-handling  and
              For buildings equipped throughout with an automatic  mechanical smoke removal  systems are  combined or
              sprinkler system in accordance with Section 903.3.1.1:  where independent building air-handling systems are pro-
              A  = V/9000                     (Equation 9-3)     vided, fans shall automatically shut down in accordance
               VR
                                                                 with the International Mechanical Code. The manual con-
              where:
                                                                 trols provided for the smoke removal system shall have the
                                                  2
              A     = The required aggregate vent area (ft ).
               VR                                                capability to override the automatic shutdown of fans that
                              3
              V     = Volume (ft ) of the area that requires smoke  are part of the smoke removal system.
                     removal.                                 910.5 Maintenance and testing. Maintenance and testing of
              For unsprinklered buildings:                    smoke and heat vents and  mechanical smoke removal sys-
              A  = A /50                      (Equation 9-4)  tems  shall be in accordance with  Sections 910.5.1 and
               VR
                    FA
                                                              910.5.2. A written record of inspection, testing and mainte-
              where:
                                                              nance  that  includes  the date, identification of personnel
                                                  2
              A     = The required aggregate vent area (ft ).  involved, any unsatisfactory result,  corrective action taken
               VR
              A FA  = The area of the floor in the area that requires  and replaced parts shall be maintained on the premises.
                     smoke removal.                              910.5.1 Smoke and heat vents. Smoke and  heat vents
         910.4 Mechanical smoke removal systems. Mechanical      shall be maintained in an operative condition. Inspection,
         smoke  removal systems shall be designed and installed  in  testing and maintenance shall be in accordance with NFPA
         accordance with Sections 910.4.1 through 910.4.7.       204 except as follows:
           910.4.1 Automatic sprinklers required.  The building    1. Mechanically operated smoke  and heat  vents  shall
           shall be equipped throughout with an approved automatic   be inspected annually and operationally  tested not
           sprinkler system in accordance with Section 903.3.1.1.    less than every 5 years.
           910.4.2 Exhaust fan construction. Exhaust fans that are  2. Gravity dropout  smoke and heat  vents shall  be
           part of a mechanical smoke removal system shall be rated  inspected annually.
           for operation at 221°F (105°C). Exhaust fan motors shall  3. Fused, damaged  or painted fusible links  shall  be
           be located outside of the exhaust fan air stream.         replaced.
           910.4.3 System design criteria. The mechanical smoke  910.5.2 Mechanical smoke removal systems. Mechani-
           removal system shall be sized to exhaust the building at a  cal smoke removal systems shall be maintained in accor-





         140                                                                        2018 INTERNATIONAL FIRE CODE ®