FIRE PROTECTION AND LIFE SAFETY SYSTEMS



              2. Sprinkler protection for the mall of a covered mall    tion 711 of the International Building Code, or
                building shall be independent from that provided for    both.
                tenant spaces or anchor buildings.
                                                                   914.3.1.1 Number of sprinkler risers and system
              3. Sprinkler protection for the tenant spaces of an open  design.  Each sprinkler system zone  in buildings that
                mall building  shall be  independent from  that pro-  are more than 420 feet (128 m) in height shall be sup-
                vided for anchor buildings.                        plied by not fewer than two risers. Each riser shall sup-
              4. Sprinkler protection shall be provided beneath exte-  ply sprinklers on alternate  floors. If more than two
                rior circulation balconies located adjacent to an open  risers are provided for a zone, sprinklers on adjacent
                mall.                                              floors shall not be supplied from the same riser.
              5. Where tenant spaces are supplied by the same sys-   914.3.1.1.1 Riser location. Sprinkler risers shall be
                tem, they shall be independently controlled.         placed in interior exit stairways and ramps that are
              Exception: An automatic sprinkler system shall not be  remotely located in accordance with Section 1007.
              required in spaces or areas of open parking garages sep-  914.3.1.2 Water supply  to required  fire pumps.  In
              arated from  the covered or open  mall in  accordance  buildings that are more than 420 feet (128 m) in build-
              with Section 402.4.2.3 of  the  International Building
                                                                   ing height, required  fire  pumps shall be supplied by
              Code and constructed in accordance with Section 406.5  connections to not fewer than two water mains located
              of the International Building Code.
                                                                   in different streets. Separate supply piping shall be pro-
           914.2.2  Standpipe  system.  The covered and open mall  vided between each connection to the water main and
           building shall be equipped  throughout with a standpipe  the pumps. Each connection and the supply piping
           system as required by Section 905.3.3.                  between the connection and the pumps shall be sized to
           914.2.3 Emergency voice/alarm communication sys-        supply the flow and pressure required for the pumps to
           tem. Where the total floor area exceeds 50,000 square feet  operate.
                  2
           (4645 m ) within either a covered mall building or within  Exception: Two connections to the same main shall
           the perimeter line of an open mall building, an emergency  be permitted provided that the main is valved such
           voice/alarm communication system shall be  provided.      that an interruption can be isolated so that the water
           Access to emergency voice/alarm communication systems     supply will continue  without interruption through
           serving a mall, required or otherwise, shall be provided for  not fewer than one of the connections.
           the fire department. The system shall be provided in accor-  914.3.2 Secondary water supply. An automatic second-
           dance with Section 907.5.2.2.
                                                                 ary on-site water supply having a capacity not less than the
           914.2.4 Fire department access to equipment. Rooms or  hydraulically calculated  sprinkler demand,  including the
           areas containing  controls  for air-conditioning systems,  hose stream requirement, shall be provided for high-rise
           automatic fire-extinguishing systems, automatic sprinkler  buildings assigned to Seismic Design Category C, D, E or
           systems or other detection, suppression or control elements  F as determined by the International Building Code. An
           shall be identified for use by the fire department.   additional fire pump shall not be required for the second-
         914.3 High-rise buildings. High-rise buildings shall comply  ary water supply unless needed to provide the minimum
         with Sections 914.3.1 through 914.3.7.                  design intake pressure at the suction side of the fire pump
                                                                 supplying the automatic sprinkler system. The secondary
           914.3.1 Automatic sprinkler system.  Buildings and    water supply shall have a duration of not less than 30 min-
           structures shall be equipped throughout with an automatic  utes as determined by the occupancy hazard classification
           sprinkler system in accordance with Section 903.3.1.1 and  in accordance with NFPA 13.
           a secondary  water supply  where required by  Section
           914.3.2.                                                Exception: Existing buildings.
              Exception: An automatic sprinkler system shall not be  914.3.3 Fire alarm system. A fire alarm system shall be
              required in spaces or areas of:                    provided in accordance with Section 907.2.12.
                1. Open parking garages in accordance with Section  914.3.4  Automatic smoke detection.  Smoke detection
                   406.5 of the International Building Code.     shall be provided in accordance with Section 907.2.12.1.
                2. Telecommunications equipment buildings used   914.3.5 Emergency voice/alarm communication sys-
                   exclusively for  telecommunications equipment,  tem.  An emergency voice/alarm communication system
                   associated electrical  power distribution  equip-  shall be provided in accordance with Section 907.5.2.2.
                   ment, batteries and standby engines, provided
                                                                 914.3.6 Emergency responder radio coverage.  Emer-
                   that those spaces or areas are equipped through-  gency responder radio  coverage shall  be provided  in
                   out with an automatic fire  detection  system in
                                                                 accordance with Section 510.
                   accordance with Section 907.2 and are separated
                                                                 914.3.7 Fire command. A fire command center comply-
                   from  the remainder  of  the building by not less
                   than 1-hour  fire barriers  constructed in accor-  ing with  Section 508 shall be provided in a  location
                                                                 approved by the fire department.
                   dance with Section  707 of the  International
                   Building Code or not less than 2-hour horizontal  914.4 Atriums. Atriums shall comply with Sections 914.4.1
                   assemblies  constructed in accordance with Sec-  and 914.4.2.