Page 181 - 2018_IFC
P. 181

FIRE PROTECTION AND LIFE SAFETY SYSTEMS



           915.4.4 Combination alarms. Combination carbon mon-  shall initiate a trouble signal at an approved location if the
           oxide/smoke alarms shall be an acceptable alternative to  power supply is interrupted.
           carbon monoxide alarms. Combination carbon monoxide/
           smoke alarms shall be listed in accordance with UL 2034  916.6 Sensor locations. Sensors shall be installed in approved
           and UL 217.                                        locations where leaking gases are expected to accumulate.
                                                              916.7 Gas sampling. Gas sampling shall be performed con-
         915.5 Carbon monoxide detection systems. Carbon monox-
         ide detection systems  shall be an acceptable alternative  to  tinuously.  Sample analysis shall be  processed  immediately
         carbon monoxide  alarms and  shall comply  with  Sections  after sampling, except as follows:
         915.5.1 through 915.5.3.                                1. For HPM gases, sample analysis shall be performed at
           915.5.1 General. Carbon monoxide detection systems      intervals not exceeding 30 minutes.
           shall comply with NFPA 720. Carbon monoxide detectors  2. For toxic gases that are not HPM, sample analysis shall
           shall be listed in accordance with UL 2075.
                                                                   be performed at intervals not exceeding 5 minutes, in
           915.5.2 Locations.  Carbon monoxide detectors shall be  accordance with Section 6004.2.2.7.
           installed in the locations specified in Section 915.2. These  3. Where a less frequent or delayed sampling interval is
           locations supersede the locations specified in NFPA 720.
                                                                   approved.
           915.5.3 Combination detectors. Combination carbon
           monoxide/smoke detectors installed in carbon monoxide  916.8 System activation. A gas detection alarm shall be initi-
           detection systems shall be an acceptable alternative to car-  ated where any sensor detects a concentration of gas exceed-
           bon monoxide detectors, provided that they are listed in  ing the following thresholds:
           accordance with UL 2075 and UL 268.                   1. For flammable gases, a gas concentration exceeding 25
         915.6 Maintenance. Carbon  monoxide  alarms and carbon    percent of the lower flammability limit (LFL).
         monoxide  detection systems shall be maintained in accor-  2. For nonflammable gases, a gas concentration exceeding
         dance with NFPA 720. Carbon monoxide alarms and carbon    one-half  of  the IDLH, unless a  different threshold  is
         monoxide detectors that become inoperable or begin produc-  specified by  the section  of this code  requiring  a gas
         ing end-of-life signals shall be replaced.                detection system.
           915.6.1 Enclosed parking  garages. Carbon  monoxide   Upon activation of a gas detection alarm, alarm signals or
           and nitrogen dioxide detectors installed in enclosed park-  other required responses shall be as specified by the section
           ing garages in accordance with the International Mechani-  of this code requiring a gas detection system. Audible and
           cal Code, Section 404.1 shall be maintained in accordance  visible alarm signals associated with  a gas detection alarm
           with the manufacturer’s instructions and their listing.  shall be distinct from fire alarm and carbon monoxide alarm
           Detectors that become inoperable or begin producing end-  signals.
           of-life signals shall be replaced.
                                                              916.9 Signage. Signs shall be provided adjacent to gas detection
   **                                                         system  alarm signaling devices that advise occupants of  the
                           SECTION 916                        nature of the signals and actions to take in response to the signal.
                    GAS DETECTION SYSTEMS
                                                              916.10 Fire alarm system connections. Gas sensors and gas
         916.1 Gas detection systems. Gas detection systems required  detection systems shall not be connected to fire alarm sys-
         by  this code shall comply with  Sections 916.2 through  tems unless approved and connected in accordance with the
         916.11.                                              fire alarm equipment manufacturer’s instructions.
         916.2 Permits. Permits shall be required as set forth in Sec-  916.11 Inspection, testing and sensor calibration. Inspec-
         tion 105.7.11.                                       tion and testing of gas detection systems shall be conducted
                                                              not less than annually. Sensor calibration shall be confirmed
           916.2.1 Construction documents. Documentation of the
           gas detection system design and equipment to be used that  at the time of sensor installation and calibration shall be per-
           demonstrates compliance with the requirements of this  formed at the frequency specified by the sensor manufacturer.
           code shall be provided with the application for permit.
         916.3 Equipment. Gas detection system equipment shall be               SECTION 917
         designed for use with the gases being detected and shall be   MASS NOTIFICATION SYSTEMS
         installed in accordance with manufacturer’s instructions.
                                                              917.1 College and university campuses. Prior to construction
         916.4 Power  connections. Gas detection systems shall be  of a new building requiring a fire alarm system on a multiple-
         permanently connected to the building electrical power sup-
         ply or shall be  permitted  to  be cord  connected to  an  building college or university  campus having a  cumulative
                                                              building occupant load of 1,000 or more, a mass notification
         unswitched receptacle using an approved restraining means
         that secures the plug to the receptacle.             risk analysis shall be conducted in accordance with NFPA 72.
                                                              Where the risk analysis determines a need for mass notifica-
         916.5  Emergency and standby power.  Standby or emer-  tion, an approved mass notification system shall be provided in
         gency power shall be provided or the gas detection system  accordance with the findings of the risk analysis.

         148                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   176   177   178   179   180   181   182   183   184   185   186