MEANS OF EGRESS



           evaluation, complying with NFPA 101, shall be done for a  aisles shall be not less than the total occupant load served
           facility utilizing the reduced width requirements of Table  by the egress element multiplied by 0.08 (2.0 mm) where
           1029.6.2 for smoke-protected assembly seating.        egress  is by stepped  aisle and multiplied by  0.06  (1.52
              Exception: For  open-air assembly  seating with  an  mm) where egress is by level aisles and ramped aisles.
              occupant load not greater than 18,000, the required  Exception:  The required capacity in inches (mm) of
              capacity in inches (mm) shall be determined using the  aisles shall be permitted to comply with Section
              factors in Section 1029.6.3.                         1029.6.2 for the number of seats in the open-air assem-
              [BE] 1029.6.2.1 Smoke control.  Aisles and  aisle    bly seating where Section 1029.6.2 permits less capac-
              accessways serving a smoke-protected assembly seat-  ity.
              ing area shall be provided with a smoke control system  [BE] 1029.7 Travel distance. The exit access travel distance
              complying with Section  909  or natural ventilation  shall comply with Section 1017. Where aisles are provided
              designed to maintain the smoke level not less than 6  for seating, the distance shall be measured along the aisles
              feet (1829 mm) above the floor of the means of egress.  and aisle accessways without travel over or on the seats.
              [BE] 1029.6.2.2 Roof height.  A  smoke-protected   Exceptions:
              assembly seating area with a roof shall have the lowest
              portion of the roof deck not less than 15 feet (4572 mm)  1. In facilities with smoke-protected assembly seating
              above the highest aisle or aisle accessway.            the total  exit access travel  distance shall be  not
                                                                     greater than 400 feet (122 m). That portion of the
                Exception:  A roof canopy  in an outdoor  stadium    total permitted exit access travel distance from each
                shall be permitted to be less than 15 feet (4572 mm)  seat  to the nearest  entrance to  a vomitory or con-
                above the highest aisle or aisle accessway provided  course shall not exceed 200 feet (60 960 mm). The
                that there are no objects less than 80 inches (2032  portion of the total permitted exit access travel dis-
                mm) above the highest aisle or aisle accessway.
                                                                     tance from  the  entrance to the  vomitory or con-
              [BE] 1029.6.2.3 Automatic sprinklers. Enclosed areas   course to one of the following shall not exceed 200
              with walls and ceilings in buildings or structures con-  feet (60 960 mm).
              taining smoke-protected assembly seating shall be pro-
              tected with an approved automatic sprinkler system in     1.1. The closest riser of an exit access stairway.
              accordance with Section 903.3.1.1.                        1.2. The closest slope of an exit access ramp.
                Exceptions:                                             1.3. An exit.
                   1. The floor area used for contests, performances  2. In facilities with open-air assembly seating of Type
                     or entertainment  provided that  the roof con-  III, IV or V construction, the total exit access travel
                     struction is more than 50 feet (15 240 mm)      distance to one of the following shall not exceed 400
                     above the floor level and the use is restricted  feet (122 m).
                     to low fire hazard uses.
                                                                        2.1. The closest riser of an exit access stairway.
                   2. Press boxes and storage facilities less than
                                        2
                     1,000 square feet (93 m ) in area.                 2.2. The closest slope of an exit access ramp.
                                                                        2.3. An exit.
                   3. Outdoor seating facilities where seating and
                     the  means of egress in the seating  area  are  3. In facilities with open-air assembly seating of Type
                     essentially open to the outside.                I or II construction, the exit access travel distance
                                                                     shall not be limited.
           [BE] 1029.6.3  Open-air assembly seating. In  open-air
           assembly seating, the required capacity in inches (mm) of

                                                    [BE] TABLE 1029.6.2
                                    CAPACITY FOR AISLES FOR SMOKE-PROTECTED ASSEMBLY
           TOTAL NUMBER OF SEATS IN                       INCHES OF CAPACITY PER SEAT SERVED
            THE SMOKE-PROTECTED     Stepped aisles with   Stepped aisles without   Level aisles or ramped aisles   Ramped aisles steeper
              ASSEMBLY SEATING    handrails within 30 inches  handrails within 30 inches  not steeper than 1 in 10 in slope  than 1 in 10 in slope
         Equal to or less than 5,000     0.200              0.250                0.150               0.165
         10,000                          0.130              0.163                0.100               0.110
         15,000                          0.096              0.120                0.070               0.077
         20,000                          0.076              0.095                0.056               0.062
         Equal to or greater than 25,000  0.060             0.075                0.044               0.048
         For SI: 1 inch = 25.4 mm.