CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS



                   installed in accordance with Section 903.3, and                   2110 of the International Build-
                                                                                                         3
                   all of the following conditions are met:                          ing Code  and having a  / -hour
                                                                                                          4
                                                                                     fire protection rating is pro-
                     2.1. For other than existing approved atriums
                         with a smoke control system, where the                      vided.
                         atrium was constructed and is maintained         2.3. Where doors are provided in the glass
                         in accordance with the code in effect at             wall,  they shall  be either self-closing or
                         the time the atrium  was created, the                automatic-closing and shall be con-
                         atrium shall have a smoke control system             structed to resist the passage of smoke.
                         that is in compliance with Section 909.
                                                                     3. In Group I-3 occupancies, exit  stairways or
                     2.2. Glass walls forming a smoke partition or      ramps and  exit access stairways or  ramps con-
                         a glass-block wall assembly shall be per-      structed in  accordance with  Section 408 in  the
                         mitted where in compliance with Condi-         International Building Code.
                         tion 2.2.1 or 2.2.2.
                                                                 1103.4.2 Three to five stories.  In other than  Group I-2
                           2.2.1. Glass  walls forming a  smoke  and I-3 occupancies, interior vertical openings connecting
                                partition shall be permitted     three to five stories shall be protected by either 1-hour fire-
                                where all of the following condi-  resistance-rated construction or an  automatic sprinkler
                                tions are met:                   system shall be installed throughout the building in accor-
                                                                 dance with Section 903.3.1.1 or 903.3.1.2.
                                  2.2.1.1. Automatic sprinklers
                                         are provided along        Exceptions:
                                         both sides of the sep-      1. Vertical  opening protection is  not required for
                                         aration  wall  and             Group R-3 occupancies.
                                         doors, or on the room
                                         side only if there is       2. Vertical  opening protection is  not required for
                                         not a walkway  or              open parking garages.
                                         occupied space on the       3. Vertical opening protection for escalators shall be
                                         atrium side.                   in accordance with Section 1103.4.5, 1103.4.6 or
                                                                        1103.4.7.
                                  2.2.1.2. The sprinklers shall
                                         be not more than 12         4. Exit access  stairways and  ramps  shall be in
                                         inches (305 mm)                accordance with Section 1103.4.8.
                                         away from  the face     1103.4.3 More than five stories. In other than Group I-2
                                         of the  glass and at    and I-3 occupancies, interior vertical openings connecting
                                         intervals along  the    more than five stories shall be protected by 1-hour fire-
                                         glass of  not greater   resistance-rated construction.
                                         than 72 inches (1829
                                         mm).                      Exceptions:
                                                                     1. Vertical  opening protection is  not required for
                                  2.2.1.3. Windows in the glass
                                         wall shall be non-             Group R-3 occupancies.
                                         operating type.             2. Vertical  opening protection is  not required for
                                                                        open parking garages.
                                  2.2.1.4. The glass wall and win-
                                         dows shall be installed     3. Vertical opening protection for escalators shall be
                                         in a gasketed frame in a       in accordance with Section 1103.4.5, 1103.4.6 or
                                         manner that the fram-          1103.4.7.
                                         ing system deflects         4. Exit access  stairways and  ramps  shall be in
                                         without breaking (load-        accordance with Section 1103.4.8.
                                         ing) the glass before the
                                         sprinkler system  oper-  1103.4.4 Atriums and covered malls. In other than
                                         ates.                   Group I-2 and I-3 occupancies, interior vertical openings
                                                                 in a covered mall building or a building with an atrium
                                  2.2.1.5. The sprinkler system  shall be  protected by  either 1-hour  fire-resistance-rated
                                         shall be designed so    construction or an  automatic sprinkler system shall be
                                         that the entire surface  installed throughout the building in accordance with Sec-
                                         of the glass is  wet    tion 903.3.1.1 or 903.3.1.2.
                                         upon activation of the
                                         sprinkler   system        Exceptions:
                                         without obstruction.        1. Vertical  opening protection is  not required for
                                                                        Group R-3 occupancies.
                           2.2.2. A  fire  barrier is not required
                                where a glass-block wall assem-      2. Vertical  opening protection is  not required for
                                bly complying with Section              open parking garages.

         202                                                                        2018 INTERNATIONAL FIRE CODE ®