CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS



             1105.10 Group I-2 automatic fire alarm system. An auto-
             matic fire alarm system shall be installed in existing Group I-
             2 occupancies in accordance with Section 907.2.6.2.
               Exception:  Manual  fire alarm boxes in patient sleeping
               areas shall not be required at exits if located at all nurses’
               control stations or other constantly attended staff loca-
               tions, provided such that manual fire alarm boxes are visi-
               ble, are provided with ready access, and travel distances
               required in Section 907.4.2.1 are not exceeded.
             1105.11  Essential electrical systems. Essential electrical
             systems  in  Group  I-2, Condition 2 occupancies shall be in
             accordance with Sections 1105.11.1 and 1105.11.2.
               1105.11.1 Where required. Where required by NFPA 99,
               Group I-2, Condition 2 occupancies shall be provided with
               an essential electrical  system in accordance with  NFPA
               99.
               1105.11.2 Installation and duration. In Group I-2, Con-
               dition 2 occupancies, the installation and duration of oper-
               ation of existing essential electrical systems shall be based
               on a hazard vulnerability analysis conducted in accordance
               with NFPA 99.

                               SECTION 1106
               REQUIREMENTS FOR OUTDOOR OPERATIONS
             1106.1 Tire storage yards. Existing tire storage yards shall
             be provided with fire apparatus access roads in accordance
             with Sections 1106.1.1 and 1106.1.2.
               1106.1.1 Access to piles. Access roadways shall be within
               150 feet (45  720 mm) of any point  in the storage  yard
               where storage piles are located not less than 20 feet (6096
               mm) from any storage pile.
               1106.1.2 Location within piles.  Fire apparatus access
               roads shall be located within all pile clearances identified
               in Section 3405.4 and within all fire breaks required in
               Section 3405.5.

































             2018 INTERNATIONAL FIRE CODE ®                                                                      215