ENERGY SYSTEMS



           1203.1.9 Maintenance. Existing  installations shall be  1203.2.10 High-rise buildings. Standby power and emer-
           maintained in accordance with the original approval and  gency power shall be provided for high-rise buildings as
           Section 1203.4.                                       required in Section 403 of the  International Building
                                                                 Code, and shall be in accordance with Section 1203.
         1203.2 Where required. Emergency and standby power sys-
         tems shall be provided where required by Sections 1203.2.1  1203.2.11  Special purpose  horizontal sliding doors.
         through 1203.2.18.                                      Standby power shall  be provided for horizontal sliding
                                                                 doors as required in  Section 1010.1.4.3. The standby
           1203.2.1 Ambulatory care facilities. Essential electrical
           systems  for ambulatory  care facilities shall be in accor-  power supply shall have a capacity to operate not fewer
           dance with  Section 422.6 of the  International Building  than 50 closing cycles of the door.
           Code.                                                 1203.2.12 Hydrogen fuel gas rooms. Standby power
                                                                 shall be provided for hydrogen fuel gas rooms as required
           1203.2.2 Elevators and  platform  lifts. Standby power
           shall  be provided for elevators and platform lifts as  by Section 5808.7.
           required in Sections 606.2, 1009.4.1, and 1009.5.     1203.2.13 Laboratory suites.  Standby or emergency
                                                                power shall be provided in accordance with Section 5004.7
           1203.2.3 Emergency responder radio coverage systems.  where laboratory suites are located above the sixth story
           Standby power shall be provided for emergency responder  above grade plane or located in a story below grade plane.
           radio coverage systems as required in Section 510.4.2.3.
           The standby power supply shall be capable of operating  1203.2.14 Means of egress illumination. Emergency
           the emergency responder radio coverage system for a   power shall be provided for means of egress illumination
           duration of not less than 24 hours.                   in accordance with Sections 1008.3 and 1104.5.1.
           1203.2.4 Emergency voice/alarm communication sys-     1203.2.15 Membrane structures. Standby power shall be
           tems. Emergency power shall be provided for emergency  provided for auxiliary inflation systems in permanent
           voice/alarm communication systems as required in Section  membrane structures in accordance with Section 2702 of
           907.5.2.2.5. The system shall be capable of powering the  the International Building Code. Auxiliary inflation sys-
           required load for a duration of not less than 24 hours, as  tems shall be provided in temporary air-supported and air-
           required in NFPA 72.                                  inflated membrane structures in accordance with Section
                                                                 3103.10.4.
           1203.2.5 Exit signs. Emergency power shall be provided
           for exit signs as required in Section 1013.6.3. The system  1203.2.16 Semiconductor fabrication facilities. Emer-
           shall be capable of powering the required load for a dura-  gency power shall be provided for semiconductor fabrica-
           tion of not less than 90 minutes.                     tion facilities as required in Section 2703.15.
           1203.2.6 Gas detection systems. Emergency power shall  1203.2.17 Smoke control systems. Standby power shall
           be provided for gas detection systems where required by  be provided for smoke control systems as required in Sec-
           Sections 1203.2.9 and 1203.2.16. Standby power shall be  tion 909.11.
           provided for gas detection systems where required by Sec-  1203.2.18 Underground  buildings. Emergency  and
           tion 916.5.                                           standby power shall be provided in underground buildings
                                                                 as required in Section 405 of the International Building
           1203.2.7 Group I-2 occupancies. Essential electrical sys-
           tems for Group I-2 occupancies shall be in accordance  Code and shall be in accordance with Section 1203.
           with Section 407.11 of the International Building Code.  1203.3 Critical circuits. Required critical circuits shall  be
                                                              protected using one of the following methods:
           1203.2.8 Group I-3 occupancies. Power-operated sliding
           doors  or power-operated locks for  swinging doors  in  1. Cables used for survivability of required critical circuits
           Group I-3 occupancies shall be operable by a manual     shall be listed in accordance with UL 2196 and shall
           release mechanism at the door. Emergency power shall be  have a fire-resistance rating of not less than 1 hour.
           provided for the doors and locks.                     2. Electrical circuit protective systems shall have a fire-
              Exceptions:                                          resistance rating of not less than 1 hour. Electrical cir-
                                                                   cuit protective systems shall be installed in accordance
                1. Emergency power is not required  in facilities  with their listing requirements.
                   where provisions for remote locking and unlock-
                   ing of occupied rooms in Occupancy Condition 4  3. Construction having a fire-resistance rating of not less
                   are not required as set forth in the International  than 1 hour.
                   Building Code.                             1203.4 Maintenance.  Emergency and  standby power sys-
                                                              tems shall be maintained in accordance with NFPA 110 and
                2. Emergency power is not required where remote
                   mechanical operating releases are provided.  NFPA 111 such that the system is capable of supplying ser-
                                                              vice within the time specified for the type and  duration
           1203.2.9 Hazardous materials. Emergency and standby  required.
           power shall be provided in  occupancies with hazardous
           materials as required in the following sections:      1203.4.1 Group  I-2. In Group  I-2 occupancies,  emer-
                                                                 gency and standby power systems shall be maintained in
              1. Sections 5004.7 and 5005.1.5 for hazardous materi-  accordance with NFPA 99.
                als.
                                                                 1203.4.2 Schedule. Inspection, testing and maintenance of
              2. Sections 6004.2.2.8 and 6004.3.4.2 for highly toxic  emergency and standby power systems shall be in accor-
                and toxic gases.                                 dance with an approved schedule established upon com-
              3. Section 6204.1.11 for organic peroxides.        pletion and approval of the system installation.