FLAMMABLE AND COMBUSTIBLE LIQUIDS



               MINIMUM DURATION   SPRINKLERS AND   HOSE STREAMS  (hours)  2      2  2  2  2  1  1  2  1  2









                MINIMUM HOSE   STREAM DEMAND  (gpm)  750  750  500  750  500  750  500  500  750  500  750






                  Maximum spacing  (square feet)  100  80  100  100  80  100  80  120  120  100  120  80




              CEILING SPRINKLER DESIGN AND DEMAND  Area (square feet)  Ordinary temperature  sprinklers  5,000  8,000  5,000  8,000  8,000  5,000  8,000  5,000  5,000  5,000  5,000  5,000









          TABLE 5704.3.6.3(4) AUTOMATIC SPRINKLER PROTECTION FOR SOLID-PILE AND PALLETIZED STORAGE OF LIQUIDS IN METAL CONTAINERS AND PORTABLE TANKS a  High-temperature  sprinklers  3,000  5,000  3,000  5,000  5,000  3,000  5,000  3,000  3,000  3,000  3,000  3,000 The design area contemplates the use of Class II standpipe systems. Where Class I standpipe systems are used, the area of application shall be increased by 30 percent without revising density.








                  Density   (gpm/ft 2 )  0.30  0.60  0.30  0.25  0.60  0.30  0.60  0.25  0.25  0.35  0.25  0.50 1 foot = 304.8 mm, 1 gallon = 3.785 L, 1 square foot = 0.0929 m 2 , 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m 2 .  For storage heights above 4 feet or ceiling heights greater than 18 feet, an approved engineering design shall be provided in accordance with Section 104.7.2.














              STORAGE CONDITIONS  Container size and arrangement 5 gallons or less, with or without cartons, palletized or  Containers greater than 5 gallons, on end or side,  5 gallons or less, with or without cartons, palletized or  Containers greater than 5 gallons on pallets or solid pile,  Containers greater than 5 gallons on pallets or solid pile,  more than one high, on end or side   5 gallons or less, with or without cartons, palletized or  Containers greater than 5 gallons o







                          solid pile b    palletized or solid pile   solid pile b    one high   Portable tanks, one high   Portable tanks, two high   solid pile   Portable tanks, one high   Portable tanks, two high




                   Class liquid      IB, IC and II  IB, IC and II


                           IA               II     II          III         For SI:  a.  b.