Page 471 - 2018_IFC
P. 471

FLAMMABLE AND COMBUSTIBLE LIQUIDS




                 MINIMUM  DURATION  SPRINKLER  AND HOSE  STREAM  (hours)  2  2  1




                 MINIMUM   HOSE   STREAM   DEMAND   (gpm)  1,000  750  500




                     Number of   sprinklers   operating  Hydraulically   most remote—  six sprinklers   at each level   Hydraulically   most remote—  six sprinklers   at each level   Hydraulically   most remote—  six sprinklers   at each level





                     Minimum   nozzle   pressure  30 psi  30 psi  15 psi


               IN-RACK SPRINKLER ARRANGEMENT AND DEMAND


                     On-end storage  (on pallets) up to   9-foot-deep racks  1. Ordinary temperature  sprinklers 8 feet apart   horizontally 2. One line sprinklers above   each tier of storage 3. Locate in longitudinal  flue space, staggered ver-  tical 4. Shields required where   multiple-level   1. See 1 above  2. See 2 above  3. See 3 above  4. See 4 above   1. See 1 above 2. One line sprinklers every  third level (maximum)  3. See 3 above  4. See 4 above






          TABLE 5704.3.6.3(6) AUTOMATIC SPRINKLER PROTECTION REQUIREMENTS FOR RACK STORAGE OF LIQUIDS IN METAL CONTAINERS GREATER THAN 5-GALLON CAPACITY a  On-side storage racks up to   9-foot-deep racks  1. Ordinary temperature  sprinklers 8 feet apart hor-  2. One line sprinklers above   each tier of storage 3. Locate in longitudinal flue  space, staggered vertical 4. Shields required where   multiple-level   1. See 1 above 2. One line sprinklers every   three tiers of storage  3.















                      Maximum  spacing  izontally  80 ft 2 /head  100 ft 2 /head  120 ft 2 /head




               CEILING SPRINKLER DESIGN AND   DEMAND  Area  (square feet)  Density  Ordinary   High-  temperature  temperature  sprinklers sprinklers  5,000  3,000  5,000  3,000  5,000  3,000

















                    CLASS  LIQUID  (gpm/ ft 2 )  0.60 (maximum  25-foot height)  IB, IC and II   0.60 (maximum  25-foot height)  0.25 (maximum  40-foot height)

                                    IA                         III       For SI:  a.


         438                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.