FLAMMABLE AND COMBUSTIBLE LIQUIDS




                      DURATION   WATER   SUPPLY   (hours)  2              MINIMUM   DURATION   SPRINKLERS  AND HOSE   STREAM   (hours)  2





                      DURATION  AFFF   SUPPLY   (minimum)  15             MINIMUM   HOSE   STREAM   DEMAND   (gpm)  500





                        Hose stream   demand d  (gpm)  500                    Number of sprinklers   operating  1. Six sprinklers each   on two levels  2. Hydraulically most  remote 12 sprinklers





                   IN-RACK SPRINKLER ARRANGEMENT AND DEMAND c
                        Number of   sprinklers   operating  Three  sprinklers per   level  Minimum nozzle   pressure  30 psi   (standard orifice)   or 14 psi (large   orifice)





                        Minimum   nozzle   pressure  (psi)  30            IN-RACK SPRINKLER ARRANGEMENT AND DEMAND  Racks 9 to   12 feet  Not  Applicable





              TABLE 5704.3.6.3(7) AUTOMATIC AFFF WATER PROTECTION REQUIREMENTS FOR RACK STORAGE OF LIQUIDS IN METAL CONTAINERS GREATER THAN 5-GALLON CAPACITY a, b  On-end storage of drums  on pallets, up to 25 feet  1. Ordinary temperature sprinkler up  to 10 feet apart horizontally 2. One line sprinklers above each   level of storage 3. Locate in longitudinal flue space,   staggered vertically 4. Shields required for multiple-level  1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot
















                          Ordinary   temperature   sprinklers  2,500  System shall be a closed-head wet system with approved devices for proportioning aqueous film-forming foam.  Maximum   spacing  100 ft 2 /head  Using extra-large orifice sprinklers under a ceiling 30 feet or less in height. Minimum aisle width is 7.5 feet.

                  CEILING SPRINKLER DESIGN   AND DEMAND  Area   (square feet)  High-  temperature   sprinklers  1,500  Except as modified herein, in-rack sprinklers shall be installed in accordance with NFPA 13. Hose stream demand includes 1 1 / 2 -inch inside hose connections, where required.  CEILING SPRINKLER DESIGN AND DEMAND  Area  (square feet)  Ordinary   High  temperature temperature  Not  2,000 b  Applicable











                         Density  (gpm/ft 2 )  0.30     The height of storage shall not exceed 25 feet.  Density  (gpm/ft 2 )  0.60  This table shall not apply to racks with solid shelves.



                        CLASS LIQUID  IA, IB,   IC and II  For SI:  L/min/m 2 .  STORAGE   HEIGHT  Maximum  20-foot storage   height  For SI:  L/min/m 2 .