CHAPTER 64

                                            PYROPHORIC MATERIALS





             User note:
                About this chapter: Chapter 64 regulates the hazards associated with pyrophoric materials, which are capable of spontaneously igniting in
                the air at or below a temperature of 130°F (54°C). Many pyrophoric materials also pose severe flammability or reactivity hazards. This chapter
                addresses only the hazards associated with pyrophoric materials. Materials that pose multiple hazards must conform to the requirements of
                this code with respect to all hazards.




                               SECTION 6401                            supply piping at the point of use or at a point where the
                                 GENERAL                               equipment using the gas is connected to the supply sys-
                                                                       tem.
             6401.1 Scope. The storage and use of pyrophoric materials
             shall be in accordance with this chapter. Compressed gases  6403.2 Quantities exceeding the maximum allowable
             shall also comply with Chapter 53.                   quantity  per control area. The storage and  use of pyro-
                                                                  phoric materials in amounts exceeding the maximum allow-
             6401.2 Permits. Permits shall be required as set forth in Sec-
             tion 105.6.                                          able quantity per control area indicated in  Section 5003.1
                                                                  shall be in accordance with Chapter 50 and this chapter.

                               SECTION 6402
                                DEFINITION                                          SECTION 6404
                                                                                      STORAGE
             6402.1 Definition. The following term is defined in Chapter
             2:                                                   6404.1 Indoor storage. Indoor storage of pyrophoric materi-
                                                                  als in amounts exceeding the  maximum allowable quantity
             PYROPHORIC.                                          per control area indicated in Table 5003.1.1(1), shall be in
                                                                  accordance with Sections 5001, 5003 and 5004 and this chap-
                                                                  ter.
                               SECTION 6403
                        GENERAL REQUIREMENTS                         The storage of silane gas, and gas mixtures with a silane
                                                                  concentration of 1.37 percent or more by volume, shall be in
             6403.1 Quantities not exceeding the maximum allowable
                                                                  accordance with CGA G-13.
             quantity per  control area.  The  storage and use of pyro-
             phoric materials in amounts not exceeding the  maximum  6404.1.1 Liquid-tight floor. In addition to the require-
             allowable quantity  per control area  indicated in Section  ments of Section 5004.12, floors of storage areas contain-
             5003.1 shall be in accordance with Sections 5001, 5003, 6401  ing pyrophoric liquids shall be of liquid-tight construction.
             and 6403.                                               6404.1.2 Pyrophoric solids and liquids. Storage of pyro-
               6403.1.1 Emergency shutoff.  Compressed gas systems   phoric solids and liquids shall be limited to a maximum
                                                                                             2
               conveying  pyrophoric gases shall be provided  with   area of 100 square feet (9.3 m ) per pile. Storage shall not
               approved manual or automatic emergency shutoff valves  exceed 5 feet (1524 mm) in height. Individual containers
               that can  be  activated  at each point  of  use and at each  shall not be stacked.
               source.                                                 Aisles between storage piles shall be not less than 10
                  6403.1.1.1 Shutoff at source. An automatic emergency  feet (3048 mm) in width.
                  shutoff valve shall be installed on supply piping at the  Individual tanks or containers shall not exceed 500 gal-
                  cylinder or  bulk source. The  shutoff valve shall  be  lons (1893 L) in capacity.
                  operated  by a remotely  located manually  activated
                  shutdown  control  located not less than 15 feet (4572  6404.1.3 Pyrophoric gases. Storage of pyrophoric gases
                  mm) from the source of supply. Manual or automatic  shall be in detached buildings where required by Section
                  cylinder valves are allowed to be used as the required  5003.8.2.
                  emergency shutoff valve where the source of supply is  6404.1.4 Separation  from incompatible materials. In
                  limited to unmanifolded cylinder sources.          addition to the requirements of Section 5003.9.8, indoor
                                                                     storage of  pyrophoric materials shall  be isolated  from
                  6403.1.1.2 Shutoff at point of use. A manual or auto-
                  matic emergency shutoff valve shall be installed on the  incompatible hazardous materials by 1-hour fire barriers