PYROPHORIC MATERIALS



           with openings protected in accordance with the Interna-              SECTION 6405
           tional Building Code.                                                     USE
              Exception: Storage in  approved hazardous materials  6405.1 General. The use of pyrophoric materials in amounts
              storage cabinets constructed in accordance with Section  exceeding the maximum allowable quantity per control area
              5003.8.7.                                       indicated in Table  5003.1.1(1) or 5003.1.1(3) shall be in
                                                              accordance with Sections 5001, 5003, 5005 and this chapter.
         6404.2 Outdoor  storage. Outdoor storage of pyrophoric
         materials in amounts exceeding the  maximum allowable  6405.2 Weather protection. Where overhead construction is
         quantity per control area indicated in Table 5003.1.1(3) shall  provided  for sheltering of  outdoor use areas of  pyrophoric
         be in accordance with Sections 5001, 5003 and 5004, and this  materials, the use areas shall be provided with approved auto-
         chapter.                                             matic fire-extinguishing system protection.
           The storage of silane gas, and gas mixtures with a silane  6405.3 Silane gas. The use of silane gas, and gas mixtures
         concentration of 1.37 percent or more by volume, shall be in  with a silane concentration of 1.37 percent or more by vol-
         accordance with CGA G-13.                            ume, shall be in accordance with CGA G-13.
           6404.2.1 Distance from storage to exposures. The sepa-
           ration of pyrophoric solids, liquids and gases from build-
           ings, lot lines, public streets, public alleys, public ways or
           means of egress shall be in accordance with the following:
              1. Solids and liquids. Two times the separation
                required by Chapter 57 for Class IB flammable liq-
                uids.
              2. Gases. The location and maximum amount of pyro-
                phoric gas  per storage area  shall be in accordance
                with Table 6404.2.1.
           6404.2.2 Weather protection. Where overhead construc-
           tion is provided for sheltering outdoor storage areas of
           pyrophoric materials, the storage areas shall be provided
           with approved automatic fire-extinguishing system protec-
           tion.



                                                      TABLE 6404.2.1
                                 PYROPHORIC GASES—DISTANCE FROM STORAGE TO EXPOSURES  a
                           MINIMUM    MINIMUM DISTANCE   MINIMUM DISTANCE  MINIMUM DISTANCE TO BUILDINGS ON THE SAME PROPERTY
            MAXIMUM                                     TO PUBLIC
           AMOUNT PER      DISTANCE   TO LOT LINES OF   STREETS, PUBLIC   Nonrated    Two-hour       Four-hour
                                       PROPERTY THAT
                          BETWEEN
          STORAGE AREA  STORAGE AREAS  CAN BE BUILT UPON  ALLEYS OR PUBLIC   construction or   construction and no  construction and no
            (cubic feet)                                  WAYS       openings within  openings within  openings within
                            (feet)         (feet)                       25 feet        25 feet        25 feet
                                                          (feet)
              250            5              25             5              5              0             0
              2,500          10             50             10             10             5             0
              7,500          20            100             20             20            10             0
                                           3
         For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m .
         a. The minimum required distances shall be reduced to 5 feet where protective structures having a minimum fire resistance of 2 hours interrupt the line of sight
           between the container and the exposure. The protective structure shall be not less than 5 feet from the exposure. The configuration of the protective structure
           shall allow natural ventilation to prevent the accumulation of hazardous gas concentrations.



















         494                                                                        2018 INTERNATIONAL FIRE CODE ®