FIRE AND SMOKE PROTECTION FEATURES



                                                      TABLE 721.1(3)—continued
                                         MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q
                                                                              THICKNESS OF FLOOR OR  MINIMUM THICKNESS OF
                                                                                   ROOF SLAB           CEILING
              FLOOR OR ROOF  ITEM               CEILING CONSTRUCTION                 (inches)           (inches)
               CONSTRUCTION  NUMBER
                                                                                4    3    2   1    4    3   2    1
                                                                              hours hours hours hour hours hours hours hour
                                   Suspended ceiling of vermiculite gypsum plaster base coat
                                   and vermiculite acoustical plaster on metal lath attached at
             9. 3" deep cellular   6" intervals to  / " cold-rolled channels spaced 12" on
                                             3
                                               4
             steel deck with       center and secured to 1 / " cold-rolled channels spaced 36"
                                                   1
                                                                                1
                                                                                                   /
                                                     2
             concrete slab on   9-1.1  on center with 0.065" (No. 16 B.W. gage) wire. 1 / "   2 / 2  —  —  —  1  1 k  —  —  —
                                                                       1
                                                                                                    8
             top. Slab thickness   channels supported by No. 8 gage wire hangers at 36" on
                                                                        2
             measured to top.                                     1
                                   center. Beams within envelope and with a 2 / " airspace
                                                                   2
                                   between beam soffit and lath have a 4-hour rating.
                 1
             10. 1 / "-deep steel
                  2
             roof deck on steel
             framing. Insulation
             board, 30 pcf         Ceiling of gypsum plaster on metal lath. Lath attached to
             density, composed     3 / " furring channels with 0.049" (No. 18 B.W. gage) wire
             of wood fibers        ties spaced 6" on center.  / " channel saddle tied to 2"
                                    4
                                                     3
             with cement           channels with doubled 0.065" (No. 16 B.W. gage) wire
                                                      4
             binders of      10-1.1  ties. 2" channels spaced 36" on center suspended 2" below   —  —  1  7 / 8  1  —  —  3 l  / 4  3  / 4 l
             thickness shown       steel framing and saddle-tied with 0.165" (No. 8 B.W.
             bonded to deck        gage) wire. Plaster mixed 1:2 by weight, gypsum-to-sand
             with unified          aggregate.
             asphalt adhesive.
             Covered with a
             Class A or B roof
             covering.
                 1
             11. 1 / "-deep steel   Ceiling of gypsum plaster on metal lath. Lath attached to
                  2
             roof deck on steel-   3 / " furring channels with 0.049" (No. 18 B.W. gage) wire
                                    4
                                                     3
             framing wood fiber    ties spaced 6" on center.  / " channels saddle tied to 2"
                                                      4
             insulation board,     channels with doubled 0.065" (No. 16 B.W. gage) wire
             17.5 pcf density on   11-1.1  ties. 2" channels spaced 36" on center suspended 2" below   —  —  1  1 /  1  —  —  7 g  /  3  /  l
             top applied over a    steel framing and saddle tied with 0.165" (No. 8 B.W.   2                 8   4
             15-lb asphalt-        gage) wire. Plaster mixed 1:2 for scratch coat and 1:3 for
             saturated felt.       brown coat, by weight, gypsum-to-sand aggregate for 1-
             Class A or B roof     hour system. For 2-hour system, plaster mix is 1:2 by
             covering.             weight, gypsum-to-sand aggregate.
                                                            (continued)