Page 201 - 2018_Complete_14_Collection (1)_Neat
P. 201

FIRE AND SMOKE PROTECTION FEATURES



                                                  TABLE 721.1(3)—continued
                                     MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q
                                                                            THICKNESS OF FLOOR   MINIMUM THICKNESS OF
                                                                              OR ROOF SLAB         CEILING
           FLOOR OR ROOF  ITEM              CEILING CONSTRUCTION                 (inches)           (inches)
           CONSTRUCTION  NUMBER
                                                                             4   3    2   1    4    3   2    1
                                                                           hours hours hours hour hours hours hours hour
         12. 1 / " deep steel
             1
              2
         roof deck on steel-
         framing insulation
         of rigid board con-
         sisting of expanded
         perlite and fibers
         impregnated with
         integral asphalt
         waterproofing; den-
         sity 9 to 12 pcf       Gypsum-vermiculite plaster on metal lath wire tied at 6"
         secured to metal       intervals to  / " furring channels spaced 12" on center and
                                        3
                   1
                                         4
         roof deck by  / "   12-1.1  wire tied to 2" runner channels spaced 32" on center.   —  —  1  —  —  —  7 / 8  —
                    2
         wide ribbons of        Runners wire tied to bottom chord of steel joists.
         waterproof, cold-
         process liquid adhe-
         sive spaced 6"
         apart. Steel joist or
         light steel construc-
         tion with metal roof
         deck, insulation,
         and Class A or B
         built-up roof cover-
         ing. e
                                Gypsum plaster over  / " Type X gypsum lath. Lath
                                               3
                                                8
                                initially applied with not less than four 1 / " by No. 13 gage
                                                            1
                                                              8
                                  19
                                by  / " head plasterboard blued nails per bearing.
                                    64
                                Continuous stripping over lath along all joist lines.
                                Stripping consists of 3" wide strips of metal lath attached
                                                   1
                                   1
                                by 1 / " by No. 11 gage by  / " head roofing nails spaced 6"
                                                    2
                                    2
                         13-1.1 on center. Alternate stripping consists of 3" wide 0.049"   —  —  —  —  —  —  —  7 / 8
                                diameter wire stripping weighing 1 pound per square yard
                                                            3
                                                       1
                                and attached by No.16 gage by 1 / " by  / " crown width
                                                        2
                                                             4
                                staples, spaced 4" on center. Where alternate stripping is
                                used, the lath nailing shall consist of two nails at each end
         13. Double wood        and one nail at each intermediate bearing. Plaster mixed
         floor over wood        1:2 by weight, gypsum-to-sand aggregate.
         joists spaced 16" on
         center. m, n           Cement or gypsum plaster on metal lath. Lath fastened
                                    1
                                                     7
                                with 1 / " by No. 11 gage by  / " head barbed shank
                                     2
                                                      16
                         13-1.2 roofing nails spaced 5" on center. Plaster mixed 1:2 for   —  —  —  —  —  —  —  5 / 8
                                scratch coat and 1:3 for brown coat, by weight, cement to
                                sand aggregate.
                                Perlite or vermiculite gypsum plaster on metal lath secured
                                                           7
                                          1
                         13-1.3 to joists with 1 / " by No. 11 gage by  / " head barbed   —  —  —  —  —  —  —  5 / 8
                                           2
                                                            16
                                shank roofing nails spaced 5" on center.
                                                      c
                                1 / " Type X gypsum wallboard nailed to joists with 5d
                                 2
                         13-1.4 cooler or wallboard nails at 6" on center. End joints of   —  —  —  —  —  —  —  1 / 2
                                    o
                                              o
                                wallboard centered on joists.
                                                        (continued)
         174                                                                    2018 INTERNATIONAL BUILDING CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   196   197   198   199   200   201   202   203   204   205   206