FIRE AND SMOKE PROTECTION FEATURES


                                                      TABLE 721.1(3)—continued
                                         MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q
                                                                              THICKNESS OF FLOOR OR  MINIMUM THICKNESS OF
                                                                                   ROOF SLAB           CEILING
                    FLOOR OR ROOF        ITEM        CEILING CONSTRUCTION            (inches)           (inches)
                    CONSTRUCTION        NUMBER
                                                                               4    3    2    1    4    3   2    1
                                                                              hours hours hours   hour  hours hours hours  hour
                                               Two layers of  / " Type X gypsum
                                                         1
                                                           2
                                               wallboard applied with the long
                                               dimension perpendicular to the I-joists
                                               with end joints staggered. The base layer
                                                            5
                                               is fastened with 1 / " Type S drywall
                                                             8
                                               screws spaced 12" o.c. and the face layer
             26. Wood I-joist (minimum I-joist   is fastened with 2" Type S drywall screws
                  1
             depth 9 / " with a minimum flange
                   4
                                               spaced 12" o.c. in the field and 8" o.c. on
                       1
             thickness of 1 / " and a minimum   26-1.1 the edges. Face layer end joints shall not   —  —  —  V  a  r  i  e  s  —  —  —  1
                        2
             flange cross-sectional area of 2.25   occur on the same I-joist as base layer
             square inches; minimum web thick-
             ness of  / ") @ 24" o.c.          end joints and edge joints shall be offset
                   3
                                               24" from base layer joints. Face layer to
                    8
                                                                         1
                                               also be attached to base layer with 1 / "
                                                                          2
                                               Type G drywall screws spaced 8" o.c.
                                               placed 6" from face layer end joints. Face
                                               layer wallboard joints to be taped and
                                               covered with joint compound.
                                               Minimum 0.019" thick resilient channel
                                               16" o.c. (channels doubled at wallboard
                                               end joints), placed perpendicular to the
                                               joist and attached to each joist by 1 / "
                                                                         1
                                                                          4
                                                                          1
                                               Type S drywall screws. Two layers of  / "
                                                                           2
                                               Type X gypsum wallboard applied with
                                               the long dimension perpendicular to the
             27. Wood I-joist (minimum I-joist   resilient channels with end joints
                                               staggered. The base layer is fastened
                  1
             depth 9 / " with a minimum flange   with 1 / " Type S drywall screws spaced
                                                    1
                   2
             depth of 1 / " and a minimum            4
                    5
                     16
             flange cross-sectional area of 1.95   27-1.1 12" o.c. and the face layer is fastened   —  —  —  V  a  r  i  e  s  —  —  —  1
                                               with 1 / " Type S drywall screws spaced
                                                    5
             square inches; minimum web thick-  12" o.c. Face layer end joints shall not
                                                     8
             ness of  / ") @ 24" o.c.          occur on the same I-joist as base layer
                   3
                    8
                                               end joints and edge joints shall be offset
                                               24" from base layer joints. Face layer to
                                                                         1
                                               also be attached to base layer with 1 / "
                                                                          2
                                               Type G drywall screws spaced 8" o.c.
                                               placed 6" from face layer end joints.
                                               Face layer wallboard joints to be taped
                                               and covered with joint compound.
                                                           (continued)







             2018 INTERNATIONAL BUILDING CODE ®                                                                  179
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   201   202   203   204   205   206   207   208   209   210   211