What happens actually during a grid faulteg.

                   Short circuit



                     Continuous Genset operation within specified operating range




                            ✓ Low voltage/ High current / bad phase angle → No active power!


                            ✓ Loading of the gas engine goes down immediately


                            ✓ Speed of the engine increases


                            ✓ Asynchrony behavior between alternator and grid could occur


                            ✓ Disconnection from the unit from the grid by the grid protection system

                                 with vector shift or df/dt relays


                            ✓ After return of the mains and stable mains conditions for xx(5) minutes,

                                 the engine will resume operation and synchronize to the grid