Page 38 - AP2464B E-BOOK (KKR2 TOWER)
P. 38

PROBLEMS




      NO PROBLEMS                                     DESCRIPTION



      1       FIRE RATED WALL RISER                   • The picture shows a fire rated wall

                                                           without the plasterboard lining and

                                                           penetrations  for fire to be stopped.












      2       FIRE RATED DOOR                         • The fire rated door are not completely

                                                           installed.

                                                      • The gap were not fully fill with firestop

                                                           materials to prevent fire from spreading
                                                           from one from to another.








      3       FIRE DAMPER                             • Unit cannot expand in fire and damper

              INSTALLATION                                 would likely jam meaning no fire
                                                           damper in the building will properly

                                                           function according to the requirements.

                                                      • When fire damper are installed, proper
                                                           clearance for expansion should be

                                                           maintained.





      4       SEALANT                                 • During the installation, the types of
              MISUNDERSTOOD                                sealant used are mistaken and cannot

                                                           function properly.

                                                      • This sealant is for stopping small gaps
                                                           and up to 3 cables , not PVC pipe.