Page 38 - AP2464B E-BOOK (KKR2 TOWER)
P. 38
PROBLEMS
NO PROBLEMS DESCRIPTION
1 FIRE RATED WALL RISER • The picture shows a fire rated wall
without the plasterboard lining and
penetrations for fire to be stopped.
2 FIRE RATED DOOR • The fire rated door are not completely
installed.
• The gap were not fully fill with firestop
materials to prevent fire from spreading
from one from to another.
3 FIRE DAMPER • Unit cannot expand in fire and damper
INSTALLATION would likely jam meaning no fire
damper in the building will properly
function according to the requirements.
• When fire damper are installed, proper
clearance for expansion should be
maintained.
4 SEALANT • During the installation, the types of
MISUNDERSTOOD sealant used are mistaken and cannot
function properly.
• This sealant is for stopping small gaps
and up to 3 cables , not PVC pipe.