Customer Power Requirement Worksheet – Option A Delta 3-Phase Power 240 VAC
It is the customer’s responsibility to make sure his Hot Runner Mold Application will not exceed the power limitations of the
DME Hot Runner Control System Main Circuit Breaker. Even though each slot may be rated at 15 amps, all slots CANNOT
necessarily deliver full power from all zones simultaneously.
PHASE A POWER PHASE B POWER PHASE C POWER
ZONE # WATTAGE ZONE # WATTAGE ZONE # WATTAGE
1 2 3
4 5 6
7 8 9
10 11 12
13 14 15
16 17 18
19 20 21
22 23 24
25 26 27
28 29 30
31 32 33
34 35 36
37 38 39
40 41 42
43 44 45
46 47 48
49 50 51
52 53 54
55 56 57
58 59 60 Control Systems | Technical Support
TOTAL PHASE A WATTS TOTAL PHASE B WATTS TOTAL PHASE C WATTS
Record Product Breaker Record Product Breaker Record Product
Size Phase Wattage Not Size Phase Wattage Not Breaker Size Phase
To Exceed To Exceed Wattage Not To Exceed
Breaker Wattage Size Table – For Delta 240 VAC 3-Phase Power
MAXIMUM PHASE WATTS MAXIMUM PHASE AMPS
BREAKER RATING AMPS EACH PHASE A,B,C EACH PHASE A,B,C
CANNOT EXCEED THIS VALUE CANNOT EXCEED THIS VALUE
10 AMP 1,386 WATTS 5.77 AMPS
20 AMP 2,771 WATTS 11.55 AMPS
30 AMP 4,157 WATTS 17.32 AMPS
40 AMP 5,542 WATTS 23.09 AMPS
50 AMP 6,928 WATTS 28.87 AMPS
63 AMP 8,729 WATTS 36.27 AMPS
70 AMP 9,699 WATTS 40.41 AMPS
100 AMP 13,856 WATTS 57.74 AMPS
For 3 Phase Delta Power: TOTAL WATTS = SquareRoot (3) x VoltsAC x AMPS
MAXIMUM PHASE WATTS = TOTAL WATTS / 3