Page 187 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 187

753-434

           8-Channel Digital Input Module 5 ... 14 V DC                                                            4

           1-conductor connection; high-side switching                                                              185


                           753-434                                    753-434
                            13 14
                 Status    A   E
                           B   F
              DI 1 ... DI 8  C  G
                           D   H
                                       Data contacts
                                                                     1    5
                  DI 1                 DI 2                    DI 1         DI 2      DI

                                                                     2    6                             DI
                  DI 3                 DI 4                    DI 3         DI 4
                                                            5 V ... 14 V          5 V ... 14 V
                                                                                        30 V    10nF
                                                                     3    7
                  DI 5                 DI 6                    DI 5         DI 6
                                                                0 V                   0 V
                                                                                            10nF    10nF
                             E
                                                                     4    8
                  DI 7                 DI 8                    DI 7         DI 8


                                       Power jumper contacts
            Delivered without miniature WSB markers          NOTE: Connection point marking (i.e., 1 ... 8) does not refer to channel assignment

           The digital input module provides 8 channels at a width of just 12mm (0.47in.).
           It receives control signals from the digital field devices (sensors, etc.).
           Each input module has a noise-rejection filter.

           Field and system levels are electrically isolated.

           Notice:
           An additional supply module must be added for operation with 5–14VDC!



           Description                 Item No.        Pack.    Technical Data
                                                       Unit
           8DI 5 (14)V DC 0.2ms  (without connector)  753-434  1  Number of inputs        8
                                                                Current consumption (internal)  4 mA
                                                                Voltage via power jumper contacts  5 V ... 14 V DC (-15 % ... +20 %)
                                                                Signal voltage (0)        -3 V DC ... 0.2 x V V
                                                                Signal voltage (1)        0.5 V V  ... 1.1 V V
                                                                Input filter              0.2 ms
                                                                Input current (typ.)      60 μA at 12 V
                                                                Input resistance          > 100 kΩ                  4.2
           Accessories                 Item No.        Pack.    Isolation                 500 V system/supply
                                                       Unit     Internal bit width        8 bits
                       753 Series Connectors  753-110  25       Wire connection           CAGE CLAMP ®
                       Coding elements  753-150        100      Cross sections            0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                                                                Strip lengths             9 ... 10 mm / 0.37 in
                       Miniature WSB Quick marking system       Width                     12 mm
                       plain           248-501         5        Weight                    41.2 g
                       with marking    see Section 11           EMC immunity of interference  acc. to EN 61131-2, marine applications
           Approvals                                            EMC emission of interference  acc. to EN 61131-2, marine applications
           Conformity marking       1
           Korea Certification
           Marine applications      GL
           r UL 508
           r ANSI/ISA 12.12.01      Class I, Div. 2, Grp. ABCD, T4
           4 TÜV 07 ATEX 554086 X   I M2 Ex d I Mb,
                                    II 3 G Ex nA IIC T4 Gc,
                                    II 3 D Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
           IECEx TUN 09.0001 X      Ex d I Mb,
                                    Ex nA IIC T4 Gc,
                                    Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C