Page 202 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 202
750-1417, 750-1418
4 8-Channel Digital Input Module 24 V DC
200 Low-side switching, 2-conductor connection
750-1417
750-1417
13 14
1
2
3
Status 4
5
DI 1 ... DI 8 6
7 Data contacts
8
1 9
DI 1 0 V
®
CAGE CLAMP S 0 V DI
connection DI 2 2 10 0 V
DI 1 … DI 8
3 11
DI 3 0 V
DI
+ 24 V + 24 V
4 12
DI 4 0 V
10nF 10nF
5 13
DI 5 0 V
0 V 0 V
6 14
DI 6 0 V 10nF
7 15
DI 7 0 V
8 16
DI 8 0 V
Power jumper contacts
The 2-conductor digital input module provides 8 channels at a width of just An optocoupler provides electrical isolation between the bus and the field side.
12mm (0.47in).
An operating tool with a 2.5mm blade (210-719) is required to open the
®
It receives binary control signals from digital field devices (e.g., sensors, CAGE CLAMP S connections.
encoders, switches or proximity switches).
®
The module has CAGE CLAMP S connections enabling solid conductors to be
inserted directly.
Each input channel has a noise-rejection RC filter with 3.0ms or 0.2 ms time
constant.
A green LED indicates the switched status of each channel.
Description Item No. Pack. Technical Data
Unit
8DI 24V DC 3.0ms, low-side switching, 750-1417 1 Number of inputs 8
2-conductor Current consumption (internal) 12 mA
8DI 24V DC 0.2ms, low-side switching, 750-1418 1 Voltage via power jumper contacts 24 V DC (-25 % ... +30 %)
2-conductor Signal voltage (0) (V V - 5 V DC) ... V V
Signal voltage (1) -3 V DC ... (V V - 15 V)
Input filter 3.0 ms (750-1417)
0.2 ms (750-1418)
Input current (typ.) -0.6 mA (at -3 V ... +5 V DC)
Accessories Item No. Pack. -2.3 mA ... -2.7 mA (at 15 V ... +32 V DC)
Unit Isolation 500 V system/field
Miniature WSB Quick marking system Wire connection CAGE CLAMP S
®
plain 248-501 5 Cross sections solid:
with marking see Section 11 0.08 mm² ... 1.5 mm² / AWG 28 ... 16
fine-stranded:
Operating tool, with partially insulated 210-719 50 0.25 mm² ... 1.5 mm² / AWG 22 ... 16
shaft, type 1, blade (2.5 x 0.4) mm Strip lengths 8 ... 9 mm / 0.33 in
Approvals Width 12 mm
Weight 45.3 g
Conformity marking 1 EMC immunity of interference acc. to EN 61000-6-2, marine applications
Korea Certification EMC emission of interference acc. to EN 61000-6-3, marine applications
Marine applications ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
4 TÜV 07 ATEX 554086 X I M2 Ex d I Mb,
II 3 G Ex nA IIC T4 Gc,
II 3 D Ex tc IIIC T135°C Dc
Permissible ambient temperature 0 °C ... +60 °C
IECEx TUN 09.0001 X Ex d I Mb,
Ex nA IIC T4 Gc,
Ex tc IIIC T135°C Dc
Permissible ambient temperature 0 °C ... +60 °C