Page 204 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 204

750-1405, 750-1406

   4    16-Channel Digital Input Module 24 V DC

  202   High-side switching


                                                                  750-1405
                               750-1405
                               13  14
                              1    2
                              3    4
                              5    6
                   Status     7    8
                              9   10
               DI 1 ... DI 16  11  12
                              13  14      Data contacts
                              15  16
                                                                  1   2
                                                          DI 1             DI 2
                                                   ®
                                          CAGE CLAMP S                                 DI
                                                                  3   4
                                          connection      DI 3             DI 4
                                          DI 1 … DI 16
                                                                  5   6
                                                          DI 5             DI 6
                                                         + 24 V                     + 24 V
                                                                  7   8
                                                          DI 7             DI 8
                                                                                             10nF     DI
                                                                  9   10
                                                          DI 9             DI 10
                                                           0 V                        0 V
                                                                  11  12
                                                         DI 11             DI 12                    10nF
                                                                  13  14
                                                         DI 13             DI 14
                                                                  15  16
                                                         DI 15             DI 16
                                          Power jumper contacts
          Delivered without miniature WSB markers
        The digital input module provides 16 channels at a width of just 12mm   An optocoupler provides electrical isolation between the bus and the field side.
        (0.47in).
        It receives binary control signals from digital field devices (e.g., sensors,
        encoders, switches or proximity switches).
                            ®
        The module has CAGE CLAMP  S connections enabling solid conductors to be
        inserted directly.
        Each input channel has a noise-rejection RC filter with 3.0ms or 0.2 ms time
        constant.
        A green LED indicates the switched status of each channel.

        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        16DI 24V DC 3.0ms            750-1405        1        Number of inputs         16
        16DI 24V DC 0.2ms            750-1406        1        Current consumption (internal)  25 mA
                                                              Voltage via power jumper contacts  24 V DC (-25 % ... +30 %)
                                                              Signal voltage (0)       -3 V ... +5 V DC
                                                              Signal voltage (1)       15 V ... 30 V DC
                                                              Input filter             3.0 ms (750-1405)
                                                                                       0.2 ms (750-1406)
                                                              Input current (typ.)     +0.6 mA (at -3 V ... +5 V DC)
        Accessories                  Item No.        Pack.                             +2.1 mA ... +2.4 mA (at 15 V ... +32 V DC)
                                                     Unit     Isolation                500 V system/field
                                                                                                ®
        Miniature WSB Quick marking system                    Wire connection          CAGE CLAMP  S
                     plain           248-501         5        Cross sections           solid:
                     with marking    see Section 11                                    0.08 mm² ... 1.5 mm² / AWG 28 ... 16
                                                                                       fine-stranded:
        Operating tool, with partially insulated   210-719  50                         0.25 mm² ... 1.5 mm² / AWG 22 ... 16
        shaft, type 1, blade (2.5 x 0.4) mm                   Strip lengths            8 ... 9 mm / 0.33 in
        Approvals                                             Width                    12 mm
                                                              Weight                   60 g
        Conformity marking        1                           EMC immunity of interference  acc. to EN 61000-6-2, marine applications
        Korea Certification         1)                        EMC emission of interference  acc. to EN 61000-6-3, marine applications
                                    1)
                                                 1)
                                          1)
        Marine applications       ABS , BV, DNV , GL, KR, LR , NKK, PRS, RINA
        r UL 508
        r ANSI/ISA 12.12.01       Class I, Div. 2, Grp. ABCD, T4
        4 TÜV 07 ATEX 554086 X    I M2 Ex d I Mb,
                                  II 3 G Ex nA IIC T4 Gc,
                                  II 3 D Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
        IECEx TUN 09.0001 X       Ex d I Mb,
                                  Ex nA IIC T4 Gc,
                                  Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
        1)
          Does not apply to 750-1406
   199   200   201   202   203   204   205   206   207   208   209