Page 207 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 207

750-415 / 753-415

           4-Channel Digital Input Module 24 V AC/DC                                                               4

           2-conductor connection                                                                                   205




                            13  14
                 Status                Status
                           A
                  DI 1         C       DI 2
                           B
                  DI 3         D       DI 4
                            E1  E2
                                       Data contacts
                                                                                      DI
                                                                    1    5
                  DI 1                 DI 2                    DI 1         DI 2
                                                                                                        1µF
                            E1  E2
                                                                    2    6            DI                  DI
                  DI 1                 DI 2                    DI 1         DI 2
                            E3  E4                                                      270pF               270pF
                                                                    3    7
                  DI 3                 DI 4                    DI 3         DI 4

                            E3 E4
                                                                    4    8
                  DI 3                 DI 4                    DI 3         DI 4
                            750-415                                  750-415

            Fig. 750 Series
            Delivered without miniature WSB markers
           The digital input module receives control signal from the digital field devices
           (sensors, etc.).
           Each input has a bridge rectifier and capacitor and current limitation for
           AC/DC operation.

           Each input module has a downstream noise-rejection filter with an integrated
           time constant.
           An optocoupler provides electrical isolation between the bus and the field side.
           All inputs are isolated.

           Description                 Item No.        Pack.    Technical Data
                                                       Unit
           4DI 24V AC/DC 20ms          750-415         1        Number of inputs          4
           4DI 24V AC/DC 20ms (without connector)  753-415  1   Current consumption (internal)  10 mA
                                                                Signal voltage (0)        -3 V ... +5 V DC; 0 V .. 5 V AC
                                                                Signal voltage (1)        11 V ... 30 V DC; 10 V .. 27 V AC
                                                                Input filter              20 ms
                                                                Input current (typ.)      7.5 mA DC; 9.5 mA AC
                                                                Isolation                 500 V system/supply ;
                                                                                          50 V channel/channel      4.2
           Accessories                 Item No.        Pack.    Internal bit width        4 bits
                                                       Unit     Wire connection           CAGE CLAMP ®
                       753 Series Connectors  753-110  25       Cross sections            0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                       Coding elements  753-150        100      Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
                                                                                          9 ... 10 mm / 0.37 in
                       Miniature WSB Quick marking system       Width                     12 mm
                       plain           248-501         5        Weight                    49.5 g
                       with marking    see Section 11           EMC immunity of interference  acc. to EN 61000-6-2, marine applications
           Approvals                                            EMC emission of interference  acc. to EN 61000-6-4, marine applications
           Conformity marking       1
           Korea Certification
           Marine applications      ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA
           r UL 508
           r ANSI/ISA 12.12.01      Class I, Div. 2, Grp. ABCD, T4
           TÜV 12.1297 X (Brasilien)  Ex nA IIC T4 Gc (750-415)
           4 TÜV 07 ATEX 554086 X   I M2 Ex d I Mb,
                                    II 3 G Ex nA IIC T4 Gc,
                                    II 3 D Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
           IECEx TUN 09.0001 X      Ex d I Mb,
                                    Ex nA IIC T4 Gc,
                                    Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
   202   203   204   205   206   207   208   209   210   211   212