Page 211 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 211

753-429

           2-Channel Digital Input Module 60 V DC                                                                  4

           2- to 4-conductor connection; high-side switching                                                        209


                           753-429                                   753-429
                            13 14
                           A
              Status DI 1      C       Status DI 2
                           B
                               D
                                       Data contacts
                  DI 1                 DI 2                         1    5
                                                               DI 1        DI 2       DI

                                                 +  —  +  —
                                       60 V                         2    6
                                                                                    60 V
                                                              60 V
                                                                                                   DI
                                                                                     10 nF/500 V
                                       0 V                          3    7
                                                                                     0 V
                                                               0 V                                    1 nF/2 kV
                             L
                                                                    4    8


                                       Power jumper contacts
            Delivered without miniature WSB markers

           The digital input module receives control signal from the digital field devices   Notice:
           (sensors, etc.).                                    An additional supply module (750-612) must be added for operation with
                                                               60VDC!
           The module is a 4-conductor device; sensors with a ground (earth) wire may be
           directly connected to the module.

           Each input module has a noise-rejection filter with a time constant.
           Field and system levels are electrically isolated.




           Description                 Item No.        Pack.    Technical Data
                                                       Unit
           2DI 60V DC 3.0ms (without connector)  753-429  1     Number of inputs          2
                                                                Max. current consumption (internal)  2.5 mA
                                                                Voltage via power jumper contacts  60 V DC (-20 % ... +25 %)
                                                                Signal voltage (0)        -7.5 V ... +12 V DC
                                                                Signal voltage (1)        44 V ... 75 V DC
                                                                Input filter              3.0 ms
                                                                Input current (typ.)      2.9 ms
                                                                Isolation                 500 V system/field        4.2
           Accessories                 Item No.        Pack.    Internal bit width        2 bits
                                                       Unit     Wire connection           CAGE CLAMP ®
                       753 Series Connectors  753-110  25       Cross sections            0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                       Coding elements  753-150        100      Strip lengths             9 ... 10 mm / 0.37 in
                                                                Width                     12 mm
                       Miniature WSB Quick marking system       Weight                    50 g
                       plain           248-501         5        EMC immunity of interference  acc. to EN 61000-6-2
                       with marking    see Section 11           EMC emission of interference  acc. to EN 61000-6-4
           Approvals
           Conformity marking       1
           r UL 508
           r ANSI/ISA 12.12.01      Class I, Div. 2, Grp. ABCD, T4
           4 TÜV 07 ATEX 554086 X   I M2 Ex d I Mb,
                                    II 3 G Ex nA IIC T4 Gc,
                                    II 3 D Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
           IECEx TUN 09.0001 X      Ex d I Mb,
                                    Ex nA IIC T4 Gc,
                                    Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
   206   207   208   209   210   211   212   213   214   215   216