Page 214 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 214

750-406 / 753-406

   4    2-Channel Digital Input Module 120 V AC

  212   2- to 4-conductor connection; high-side switching




                         13  14
                         A
            Status DI 1      C       Status DI 2
                         B
                             D
                         13  14      Data contacts
                                                                  1   5
                DI 1                 DI 2                   DI 1         DI 2      DI
                                                                                          100nF
                          L   L
                                                                                                        DI
                                               +  —   +  —        2   6
                                     120 V                                       120 V
                                                           120 V                       U
                         N  N
                                                                  3   7
                                     N                                              N
                                                              N


                                                                  4   8

                          750-406                                  750-406
                                     Power jumper contacts
          Fig. 750 Series
          Delivered without miniature WSB markers
        The digital input module receives control signal from the digital field devices
        (sensors, etc.).
        The module is a 4-conductor device; sensors with a ground (earth) wire may be
        directly connected to the module.

        Field and system levels are electrically isolated.

        Notice:
        An additional supply module must be added for operation with 120VAC!


        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        2DI 120V AC                  750-406         1        Number of inputs         2
        2DI 120V AC (without connector)  753-406     1        Current consumption (internal)  2 mA
                                                              Voltage via power jumper contacts  230 V AC  (-15 % ... +20 %);
                                                                                       (± 20 % 1.5 s)
                                                              Signal voltage (0)       0 V ... 20 V AC
                                                              Signal voltage (1)       79 V AC ... 1.1 V N
                                                              Input filter             10 ms
                                                              Input current (typ.)     4.5 mA
        Accessories                  Item No.        Pack.    Input frequency          f (nominal) ± 10 %
                                                     Unit                              50 Hz ± 10 %
                     753 Series Connectors  753-110  25                                60 Hz ± 10 %
                     Coding elements  753-150        100      Isolation                1.5 kV eff. (field/system)*;
                                                                                       * 2.5 kV rated surge voltage;
                     Miniature WSB Quick marking system                                Overvoltage category III
                     plain           248-501         5        Internal bit width       2 bits
                     with marking    see Section 11           Wire connection          CAGE CLAMP ®
        Approvals                                             Cross sections           0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                                                              Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
        Conformity marking        1                                                    9 ... 10 mm / 0.37 in
        Korea Certification                                   Width                    12 mm
        Marine applications       ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA  Weight     48.5 g
        r UL 508                                              EMC immunity of interference  acc. to EN 61000-6-2, marine applications
        r ANSI/ISA 12.12.01       Class I, Div. 2, Grp. ABCD, T4  EMC emission of interference  acc. to EN 61000-6-4, marine applications
        4 TÜV 07 ATEX 554086 X    I M2 Ex d I Mb,
                                  II 3 G Ex nA IIC T4 Gc,
                                  II 3 D Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
        IECEx TUN 09.0001 X       Ex d I Mb,
                                  Ex nA IIC T4 Gc,
                                  Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
   209   210   211   212   213   214   215   216   217   218   219