Page 215 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 215

753-440

           4-Channel Digital Input Module 120 (230) V AC                                                           4

           2-conductor connection; high-side switching                                                              213


                           753-440                                   753-440
                            13 14
                 Status                Status
                           A
                   DI 1        C       DI 2
                           B
                  DI 3         D       DI 4
                                       Data contacts                1    5
                  DI 1                 DI 2                    DI 1         DI 2      DI
                                                                                            100nF
                                                                    2    6               U
                                       120 (230) V           120 V                 120 V
                                                            (230 V)               (230 V)
                                                                                                        DI
                                                                    3    7
                                       120 (230) V
                                                                N                     N
                             L
                                                                    4    8
                  DI 3                 DI 4                    DI 3         DI 4


                                       Power jumper contacts
            Delivered without miniature WSB markers

           The digital input module receives control signal from the digital field devices
           (sensors, etc.).
           The module is a 4-channel, 2-conductor device and four sensors may be directly
           connected to it.

           Field and system levels are electrically isolated.

           Notice:
           An additional supply module must be added for operation with
           120 (230) VAC!

           Description                 Item No.        Pack.    Technical Data
                                                       Unit
           4DI 120 (230)V AC 10ms  (without   753-440  1        Number of inputs          4
           connector)                                           Current consumption (internal)  15 mA
                                                                Voltage via power jumper contacts  90 V ... 230 V AC (-15 % ... +10 %)
                                                                Signal voltage (0)        0 V ... 40 V AC
                                                                Signal voltage (1)        79 V ... 230 V AC (-15 % ... +10 %)
                                                                Input filter              10 ms
                                                                Overvoltage protection    AC 275 V varistor
                                                                Input current (typ.)      2.3 mA at 120 V; 4.7 mA at 230 V  4.2
           Accessories                 Item No.        Pack.    Input frequency           f (nominal) ± 10 %;
                                                       Unit                               50 Hz ± 10 % at 230 V;
                       753 Series Connectors  753-110  25                                 60 Hz ± 10 % at 120 V
                       Coding elements  753-150        100      Isolation                 1.5 kV eff. (field/system)*;
                                                                                          * 2.5 kV rated surge voltage;
                       Miniature WSB Quick marking system                                 Overvoltage category III
                       plain           248-501         5        Internal bit width        4 bits
                       with marking    see Section 11           Wire connection           CAGE CLAMP ®
           Approvals                                            Cross sections            0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                                                                Strip lengths             9 ... 10 mm / 0.37 in
           Conformity marking       1                           Width                     12 mm
           Korea Certification                                  Weight                    43.5 g
           r UL 508                                             EMC immunity of interference  acc. to EN 61000-6-2
           r ANSI/ISA 12.12.01      Class I, Div. 2, Grp. ABCD, T4  EMC emission of interference  acc. to EN 61000-6-4
           4 TÜV 07 ATEX 554086 X   I M2 Ex d I Mb,
                                    II 3 G Ex nA IIC T4 Gc,
                                    II 3 D Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
           IECEx TUN 09.0001 X      Ex d I Mb,
                                    Ex nA IIC T4 Gc,
                                    Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
   210   211   212   213   214   215   216   217   218   219   220