Page 217 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 217
750-425 / 753-425
2-Channel Digital Input Module NAMUR 4
Proximity switch acc. to DIN EN 60947-5-6 215
13 14
A
Status DI 1 C Status DI 2
B
Error DI 1 D Error DI 2
01 03
Data contacts
blue(-) 1 5
DI 1 DI 2 DI 1 DI 2 DI
+ +
270pF
Eval-
A 2 6 uation
24 V 24 V
+ 24 V
— — Sensor
supply
3 7 Error
0 V 0 V Status
0 V 10nF
02 04
270pF
4 8
U V 1 U V 2 U V 1 U V 2 U V
brown(+)
750-425 750-425
Power jumper contacts
Fig. 750 Series
Delivered without miniature WSB markers
The digital input module receives control signals from NAMUR proximity
switches (based on DIN EN 60947-5-6) in the field.
The voltage supply of each channel of the sensors is delivered by a short circuit
proof 8.2V voltage source. A short circuit or a line break is indicated in the
process image (1 bit) and via the red LED.
The green LED indicates the input status:
• Signal current (0) LED off
• Signal current (1) LED on
Field and system levels are electrically isolated.
Description Item No. Pack. Technical Data
Unit
2DI NAMUR 750-425 1 Number of inputs 2
2DI NAMUR (without connector) 753-425 1 Current consumption typ. (internal) 5 mA
Voltage via power jumper contacts 24 VDC (-25 % ... +30 %)
Signal current (0) ≤ 1.2 mA
Signal current (1) ≥ 2.1 mA
Input filter 3.0 ms
Switching hysteresis 0.2 mA
Open-circuit voltage 8.2 VDC 4.2
Accessories Item No. Pack. Input resistance 1 kΩ
Unit Input pulse duration ≥ 5 ms
753 Series Connectors 753-110 25 Input pulse separation ≥ 3 ms
Coding elements 753-150 100 Short-circuit current ≤ 8.2 mA
Short-circuit monitoring > 6.5 mA
Miniature WSB Quick marking system Line break monitoring < 0.2 mA
plain 248-501 5 Sensor supply V V 8.2 VDC
with marking see Section 11 Isolation 500 V system/supply
Approvals Internal bit width 4 bits in, 2 bits data, 2 bits error (short
circuit/line break)
Conformity marking 1 Wire connection CAGE CLAMP ®
Korea Certification Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Marine applications ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA Strip lengths, 750/753 Series 8 ... 9 mm / 0.33 in
r UL 508 9 ... 10 mm / 0.37 in
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4 Width 12 mm
TÜV 12.1297 X (Brasilien) Ex nA IIC T4 Gc (750-425) Weight 51 g
4 TÜV 07 ATEX 554086 X I M2 Ex d I Mb, EMC immunity of interference acc. to EN 61000-6-2, marine applications
II 3 G Ex nA IIC T4 Gc, EMC emission of interference acc. to EN 61000-6-4, marine applications
II 3 D Ex tc IIIC T135°C Dc
Permissible ambient temperature 0 °C ... +60 °C
IECEx TUN 09.0001 X Ex d I Mb,
Ex nA IIC T4 Gc,
Ex tc IIIC T135°C Dc
Permissible ambient temperature 0 °C ... +60 °C