Page 218 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 218

750-424 / 753-424

   4    Intruder Detection

  216




                       13  14
                       A
           Status DI 1    C      Status DI 2
                       B
            Error DI 1    D      Error DI 2
                       01  02                                                                  U ref 1
                                 Data contacts                                                        Error
                                          Alarm contact
                                       ld                         1   5
               DI 1              DI 2                       DI 1         DI 2    DI
                       +  +               R1
                                                                                         270pF
                                                                  2   6
                                 24 V      R2                                  24 V
                                                            24 V
                       —  —                                                                    U ref 2   Status
                                                                                      10nF
                                     R wire                       3   7
                                 0 V                                            0 V
                                                             0 V                    10nF
                                                                                               U ref 3
                                                                  4   8

                       750-424                                     750-424
                                 Power jumper contacts
          Fig. 750 Series
          Delivered without miniature WSB markers
        This module incorporates a current loop which makes it possible to monitor
        alarm contacts with a fixed resistance ratio (R1, R2), for intruder detection.
        The module indicates the current status of the contact via LEDs and via status
        bits in the process image.









        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        2DI 24V DC Intruder Detection  750-424       1        Number of inputs         2
        2DI 24V DC Intruder Detection (without   753-424  1   Current consumption typ. (internal)  6 mA
        connector)                                            Current consumption max. (field side)  16 mA/24 V DC
                                                              Voltage via power jumper contacts  24 V DC (-25 % ... +30 %)
                                                              Loop current typ. (ld)   1 mA
                                                              R1                       1.5 kΩ (± 5 %)
                                                              R2                       2.2 kΩ (± 5 %)
                                                              R wire (max.)            200 Ω
        Accessories                  Item No.        Pack.    Isolation                500 V system/supply
                                                     Unit     Internal bit width       4 bits
                     753 Series Connectors  753-110  25       Wire connection          CAGE CLAMP ®
                     Coding elements  753-150        100      Cross sections           0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                                                              Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
                     Miniature WSB Quick marking system                                9 ... 10 mm / 0.37 in
                     plain           248-501         5        Width                    12 mm
                     with marking    see Section 11           Weight                   36 g
        Approvals                                             EMC immunity of interference  acc. to EN 61000-6-2, marine applications
                                                              EMC emission of interference  acc. to EN 61000-6-4, marine applications
        Conformity marking        1
        Korea Certification
        Marine applications       ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA
        r UL 508
        r ANSI/ISA 12.12.01       Class I, Div. 2, Grp. ABCD, T4
        TÜV 12.1297 X (Brasilien)  Ex nA IIC T4 Gc (750-424)
        4 TÜV 07 ATEX 554086 X    I M2 Ex d I Mb,
                                  II 3 G Ex nA IIC T4 Gc,
                                  II 3 D Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
        IECEx TUN 09.0001 X       Ex d I Mb,
                                  Ex nA IIC T4 Gc,
                                  Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
   213   214   215   216   217   218   219   220   221   222   223