Page 212 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 212

750-427 / 753-427

   4    2-Channel Digital Input Module 110 V DC

  210   Configurable high-side or low-side switching




                         13 14
                         A
           Status DI 1       C
                         B
           Status DI 2       D
                         01  03
                                    Data contacts                                  DI+             I    DI
                                                                   1   5
                DI 1                DI 2                     DI 1         DI 2         10nF
                         +  +
                                                                                   DI-
                                                                   2   6
                                    110 V
                                                            110 V                110 V
                         —  —            Low-side  High-side
                                        application  application
                                                                                              4,7nF
                                                                   3   7
                                    0 V
                                                             0 V                   0 V
                                                                                                  4,7nF
                         02  04
                                                                   4   8
                DI 1                DI 2                     DI 1         DI 2
                         750-427                                   750-427
                                    Power jumper contacts
          Fig. 750 Series
          Delivered without miniature WSB markers
        The digital input module receives control signal from the digital field devices
        (sensors, etc.).
        The module is a 2-channel device. Each channel can be used as a high-side or
        low-side switching input, depending on the external wiring.

        Field and system levels are electrically isolated.

        Notice:
        An additional supply module must be added for operation with 110VDC!


        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        2DI 110V DC                  750-427         1        Number of inputs         2
        2DI 110V DC (without connector)  753-427     1        Current consumption (internal)  2.5 mA
                                                              Voltage via power jumper contacts  110 V DC (-20 % ... +25 %)
                                                              Signal voltage (0)       < 50V
                                                              Signal voltage (1)       > 70V
                                                              Input filter             3.0 ms
                                                              Input current (typ.)     2.5 mA
                                                              Isolation                1.5 kV eff. (field/system)*;
        Accessories                  Item No.        Pack.                             * 2.5 kV rated surge voltage;
                                                     Unit                              Overvoltage category III
                     753 Series Connectors  753-110  25       Internal bit width       2 bits
                     Coding elements  753-150        100      Wire connection          CAGE CLAMP ®
                                                              Cross sections           0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                     Miniature WSB Quick marking system       Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
                     plain           248-501         5                                 9 ... 10 mm / 0.37 in
                     with marking    see Section 11           Width                    12 mm
        Approvals                                             Weight                   48.3 g
                                                              EMC immunity of interference  acc. to EN 61000-6-2
        Conformity marking        1                           EMC emission of interference  acc. to EN 61000-6-3
        Korea Certification
        r UL 508
        r ANSI/ISA 12.12.01       Class I, Div. 2, Grp. ABCD, T4
        TÜV 12.1297 X (Brasilien)  Ex nA IIC T4 Gc (750-427)
        4 TÜV 07 ATEX 554086 X    I M2 Ex d I Mb,
                                  II 3 G Ex nA IIC T4 Gc,
                                  II 3 D Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
        IECEx TUN 09.0001 X       Ex d I Mb,
                                  Ex nA IIC T4 Gc,
                                  Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
   207   208   209   210   211   212   213   214   215   216   217