Page 209 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 209

750-428 / 753-428

           4-Channel Digital Input Module 42 V AC/DC                                                               4

           2-conductor connection                                                                                   207




                            13  14
                 Status                Status
                           A
                  DI 1         C       DI 2
                           B
                  DI 3         D       DI 4
                            E1  E2                                                    DI
                                       Data contacts
                                                                    1    5
                  DI 1                 DI 2                    DI 1         DI 2
                                                                                                          DI
                            E1 E2
                                                                                      DI
                                                                    2    6
                  DI 1                 DI 2                    DI 1         DI 2
                                                                                        270pF               270pF
                            E3  E4
                                                                    3    7
                  DI 3                 DI 4                    DI 3         DI 4
                            E3  E4
                                                                    4    8
                  DI 3                 DI 4                    DI 3         DI 4
                            750-428                                  750-428

            Fig. 750 Series
            Delivered without miniature WSB markers
           The digital input module receives control signal from the digital field devices
           (sensors, etc.).
           Each input module has a noise-rejection filter with a time constant.

           Field and system levels are electrically isolated.
           All inputs are isolated.





           Description                 Item No.        Pack.    Technical Data
                                                       Unit
           4DI 42V AC/DC 20ms          750-428         1        Number of inputs          4
           4DI 42V AC/DC 20ms (without connector)  753-428  1   Current consumption (internal)  5 mA
                                                                Signal voltage (0)        -3 V ... +10 V DC; 0 V ... 10 V AC
                                                                Signal voltage (1)        30 V ... 53 V DC; 30 V ... 53 V AC
                                                                Input filter              20 ms
                                                                Input current (typ.)      3.6 mA DC; 6.0 mA AC
                                                                Isolation                 500 V AC system/supply;
                                                                                          500 V AC channel/channel  4.2
           Accessories                 Item No.        Pack.    Internal bit width        4 bits
                                                       Unit     Wire connection           CAGE CLAMP ®
                       753 Series Connectors  753-110  25       Cross sections            0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                       Coding elements  753-150        100      Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
                                                                                          9 ... 10 mm / 0.37 in
                       Miniature WSB Quick marking system       Width                     12 mm
                       plain           248-501         5        Weight                    49.5 g
                       with marking    see Section 11           EMC immunity of interference  acc. to EN 61000-6-2
           Approvals                                            EMC emission of interference  acc. to EN 61000-6-4
           Conformity marking       1
           Korea Certification
           r UL 508
           r ANSI/ISA 12.12.01      Class I, Div. 2, Grp. ABCD, T4
           4 TÜV 07 ATEX 554086 X   I M2 Ex d I Mb,
                                    II 3 G Ex nA IIC T4 Gc,
                                    II 3 D Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
           IECEx TUN 09.0001 X      Ex d I Mb,
                                    Ex nA IIC T4 Gc,
                                    Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C