Page 226 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 226
750-506 / 753-506
4 2-Channel Digital Output Module 24 V DC
224 Short-circuit protected; high-side switching; with diagnostics
13 14
A
Status DO 1 C Status DO 2
B
Error DO 1 D Error DO 2
13 14
Data contacts
1 5
DO 1 DO 2 DO 1 DO 2 DO
+ +
270pF
2 6 Error
24 V 24 V
24 V
— — 10nF DO
3 7
0 V 0 V
0 V 10nF
4 8
750-506 750-506
Power jumper contacts
Fig. 750 Series
Delivered without miniature WSB markers
Control signals are transmitted from the automation device to connected Field and system levels are electrically isolated.
actuators via the digital output module.
All outputs are short-circuit proof.
In addition to the functions that can be fulfilled by the standard output modules,
these output modules can recognize a short circuit or an open circuit.
The status is transmitted to the fieldbus couplers and indicated by LEDs.
The I/O module is a 4-conductor device and actuators with ground (earth)
connection may be directly connected to it.
Description Item No. Pack. Technical Data
Unit
2DO 24V DC 0.5A/ diagnostics 750-506 1 No. of outputs 2
2DO 24V DC 0.5A/ diagnostics/R* 750-506/000-800 1 Current consumption (internal) 15 mA
* /R: Interference-free for safety function applications (see manual) Voltage via power jumper contacts 24 V DC (-15 % ... +20 %)
2DO 24V DC 0.5A/ diagnostics (without 753-506 1 Type of load resistive, inductive, lamps
connector) Max. switching frequency 5 kHz
Reverse voltage protection no
Output current (max.) 0.5 A
Short-circuit limitation (typ.) Pwm 1.5 A
Accessories Item No. Pack. Open-circuit detection < 9.5 mA
Unit Diagnostics Open circuit, overload and short-circuit
753 Series Connectors 753-110 25 Inductive load switch off energy
Coding elements 753-150 100 dissipation W (max.) 0.2 J; L max = 2 x W max / I 2
Current consumption typ. (field side) 15 mA / module + charge
Miniature WSB Quick marking system Isolation 500 V system/supply
plain 248-501 5 Internal bit width 4 bits in, 4 bits out
with marking see Section 11 Wire connection CAGE CLAMP ®
Approvals Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Strip lengths, 750/753 Series 8 ... 9 mm / 0.33 in
Conformity marking 1 9 ... 10 mm / 0.37 in
Korea Certification Width 12 mm
r UL 508 Weight 49.5 g
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4 EMC immunity of interference acc. to EN 61000-6-2
4 TÜV 07 ATEX 554086 X I M2 Ex d I Mb, EMC emission of interference acc. to EN 61000-6-4
II 3 G Ex nA IIC T4 Gc,
II 3 D Ex tc IIIC T135°C Dc
Permissible ambient temperature 0 °C ... +60 °C
IECEx TUN 09.0001 X Ex d I Mb,
Ex nA IIC T4 Gc,
Ex tc IIIC T135°C Dc
Permissible ambient temperature 0 °C ... +60 °C