Page 226 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 226

750-506 / 753-506

   4    2-Channel Digital Output Module 24 V DC

  224   Short-circuit protected; high-side switching; with diagnostics




                         13  14
                         A
           Status DO 1       C       Status DO 2
                         B
           Error DO 1        D       Error DO 2
                         13 14
                                     Data contacts
                                                                  1   5
               DO 1                  DO 2                   DO 1         DO 2   DO
                          +  +
                                                                                   270pF
                                                                  2   6                      Error

                                     24 V                                      24 V
                                                            24 V
                          —  —                                                    10nF   DO
                                                                  3   7
                                     0 V                                        0 V
                                                             0 V                        10nF

                                                                  4   8

                          750-506                                  750-506
                                     Power jumper contacts
          Fig. 750 Series
          Delivered without miniature WSB markers
        Control signals are transmitted from the automation device to connected   Field and system levels are electrically isolated.
        actuators via the digital output module.
        All outputs are short-circuit proof.

        In addition to the functions that can be fulfilled by the standard output modules,
        these output modules can recognize a short circuit or an open circuit.
        The status is transmitted to the fieldbus couplers and indicated by LEDs.
        The I/O module is a 4-conductor device and actuators with ground (earth)
        connection may be directly connected to it.


        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        2DO 24V DC 0.5A/ diagnostics  750-506        1        No. of outputs           2
        2DO 24V DC 0.5A/ diagnostics/R*  750-506/000-800  1   Current consumption (internal)  15 mA
        * /R: Interference-free for safety function applications (see manual)  Voltage via power jumper contacts  24 V DC (-15 % ... +20 %)
        2DO 24V DC 0.5A/ diagnostics (without   753-506  1    Type of load             resistive, inductive, lamps
        connector)                                            Max. switching frequency  5 kHz
                                                              Reverse voltage protection  no
                                                              Output current (max.)    0.5 A
                                                              Short-circuit limitation (typ.) Pwm  1.5 A
        Accessories                  Item No.        Pack.    Open-circuit detection   < 9.5 mA
                                                     Unit     Diagnostics              Open circuit, overload and short-circuit
                     753 Series Connectors  753-110  25       Inductive load switch off energy
                     Coding elements  753-150        100      dissipation W (max.)     0.2 J; L max = 2 x W max / I 2
                                                              Current consumption typ. (field side)  15 mA / module + charge
                     Miniature WSB Quick marking system       Isolation                500 V system/supply
                     plain           248-501         5        Internal bit width       4 bits in, 4 bits out
                     with marking    see Section 11           Wire connection          CAGE CLAMP ®
        Approvals                                             Cross sections           0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                                                              Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
        Conformity marking        1                                                    9 ... 10 mm / 0.37 in
        Korea Certification                                   Width                    12 mm
        r UL 508                                              Weight                   49.5 g
        r ANSI/ISA 12.12.01       Class I, Div. 2, Grp. ABCD, T4  EMC immunity of interference  acc. to EN 61000-6-2
        4 TÜV 07 ATEX 554086 X    I M2 Ex d I Mb,             EMC emission of interference  acc. to EN 61000-6-4
                                  II 3 G Ex nA IIC T4 Gc,
                                  II 3 D Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
        IECEx TUN 09.0001 X       Ex d I Mb,
                                  Ex nA IIC T4 Gc,
                                  Ex tc IIIC T135°C Dc
              Permissible ambient temperature 0 °C ... +60 °C
   221   222   223   224   225   226   227   228   229   230   231