Page 227 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 227

750-508 / 753-508

           2-Channel Digital Output Module 24 V DC                                                                 4

           Short-circuit protected; high-side switching; with diagnostics                                           225




                            13  14
                           A
             Status DO 1       C       Status DO 2
                           B
              Error DO 1       D       Error DO 2
                           13  14
                                       Data contacts
                                                                    1    5
                 DO 1                  DO 2                   DO 1         DO 2   DO
                                                                                                      Status
                            +  +
                                                                                     270pF                    µC
                                                                    2    6                                 Status
                                       24 V                                      24 V                      Diag.
                                                              24 V
                                                                                                    Diagnostics
                            —  —
                                                                                    10nF  10nF
                                                                    3    7
                                       0 V                                        0 V
                                                               0 V
                                                                                               10nF
                                                                    4    8
                            750-508                                  750-508
                                       Power jumper contacts
            Fig. 750 Series
            Delivered without miniature WSB markers
           Control signals are transmitted from the automation device to connected   Field and system levels are electrically isolated.
           actuators via the digital output module.
           All outputs are short-circuit proof.

           In addition to the functions that can be fulfilled by the standard output modules,
           these output modules can recognize a short circuit or an open circuit.
           The status is transmitted to the fieldbus couplers and indicated by LEDs.
           The I/O module is a 4-conductor device and actuators with ground (earth)
           connection may be directly connected to it.


           Description                 Item No.        Pack.    Technical Data
                                                       Unit
           2DO 24V DC 2.0A, diagnostics  750-508       10 1)    No. of outputs            2
           2DO 24V DC 2.0A/ diagnostics/R*  750-508/000-800  1  Current consumption (internal)  14 mA
           * /R: Interference-free for safety function applications (see manual)  Voltage via power jumper contacts  24 V DC (-25 % ... +30 %)
           2DO 24V DC 2.0A/ diagnostics (without   753-508  1   Type of load              resistive, inductive, lamps
           connector)                                           Max. switching frequency  1 kHz
                                                                Reverse voltage protection  yes
                                                                Output current (max.)     2A
           1)
            Also available individually                         Short-circuit limitation (typ.) Pwm  15A / 2s
           Accessories                 Item No.        Pack.    Open-circuit detection    < 0.2 mA
                                                       Unit     Diagnostics               Open circuit, overload and short-circuit
                       753 Series Connectors  753-110  25       Current consumption typ. (field side)  7 mA / module + charge
                       Coding elements  753-150        100      Isolation                 500 V system/supply
                                                                Internal bit width        2 bits in; 2 bits out
                       Miniature WSB Quick marking system       Wire connection           CAGE CLAMP ®              4.3
                       plain           248-501         5        Cross sections            0.08 mm² ... 2.5 mm² / AWG 28 ... 14
                       with marking    see Section 11           Strip lengths, 750/753 Series  8 ... 9 mm / 0.33 in
           Approvals                                                                      9 ... 10 mm / 0.37 in
                                                                Width                     12 mm
           Conformity marking       1                           Weight                    48.7 g
           Korea Certification                                  EMC immunity of interference  acc. to EN 61000-6-2, marine applications
           Marine applications (versions upon request)  ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA  EMC emission of interference  acc. to EN 61000-6-3, marine applications
           r UL 508
           r ANSI/ISA 12.12.01      Class I, Div. 2, Grp. ABCD, T4
           4 TÜV 07 ATEX 554086 X   I M2 Ex d I Mb,
                                    II 3 G Ex nA IIC T4 Gc,
                                    II 3 D Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C
           IECEx TUN 09.0001 X      Ex d I Mb,
                                    Ex nA IIC T4 Gc,
                                    Ex tc IIIC T135°C Dc
                 Permissible ambient temperature 0 °C ... +60 °C