1    Relay Modules in DIN-Rail Mount Enclosure



  104
                                            Relay with 1 make contact (1 a)
                                            Nominal input voltage V : 24 V, 230 V AC
                                                             N
                                            for lamp loads




                 100                                                           Contact life,      Capability  Electrical life
              Switching current (A)       10  AC resistive load                Incandescent lamp  2200 W  20,000
                                                                               type of load
                                                                                                          50,000
                                                                                                  1400 W
                                                                               Halogen lamp 230 VAC
                                                                                                  120 VA
                                                                                                          20,000
                                                                               Halogen trafo
                                                                               Fluorescent lamp not comp., CCG !,
                                                                               cos ϕ 0.406
                                                                                                  20 x 58 W
                                                                                                          25,000
                                                                               Fluorescent lamp comp., CCG !, C parallel
                                                                                                  600 W
                                                                                                          20,000
                                                                               Fluorescent lamp comp., CCG !, Duo-circuit  9 x 58 W   25,000
                  DC resistive load                                            Fluorescent lamp with  ECG "   12 x 58 W   25,000
                                                                                                          20,000
                     1                                                         Energy saving lamp 15 W  25 pcs
                                                                               Energy saving lamp 13 W  30 pcs  20,000
                                                                                                          20,000
                                                                               Energy saving lamp 9 W  38 pcs
                                                                                                  1000 W  20,000
                                                                               Gas discharge lamp
                                                                                                  800 W   20,000
                                                                               Dulux-Lamp not compensated
                                                                                                  500 W   20,000
                                                                               Dulux-Lamp compensated
                                     10               100              1000    Max. capacitance at 230 VAC   60 μF   > 5,000
                          Switching voltage (V)                                ! CCG = Conventional Control Gear
                                                                               " ECG  = Electronic Control Gear
        Load limit curve                    Similiar to picture
                                                                   14
                                               A1
                                               ~
                                               A2
        Note: Inductive loads have to be attenuated by an   ~
        appropriate protective circuit in order to protect relay coils   A2  13 13
        and contacts.
                                               ~
        Description                                           Item No.   Pack.
                                                                         Unit
                                                       I N
                                            V N
        Relay module in DIN-rail mount enclosure,   24 VAC  32 mA  789-520  1
        for DIN 35 rail                    230 VAC     15 mA  789-321    1
        Technical Data                              Accessories see pages 115
        Coil:
          Input voltage range                          V N  -15 % ... +20 %
        Contacts:
          Contact material                                Ag alloy
          Max. continuous current                          16 A
          Max. make current                           120 A / 50 ms (AC)
          Max. switching voltage                          250 VAC
          Max. switching power (resistive)          4 kVA AC, DC see load curve
          Recommended minimum load                    12 V AC/DC, 100 mA
          Pull-in/drop-out/bounce time typ.             15ms / 5ms / -
          Mechanical life                           10 x 10  switching operations
                                                        6
        General specifications:
          Nominal voltage to EN 60664-1                250 V / 4 kV / 3
          Dielectric strength, contact-coil (AC, 1 min)   4 kV rms
          Dielectric strength open contact (AC, 1 min)    1 kV rms
          Dielectric strength contact-contact (AC, 1 min)   -
                                                       -25 °C ... +40 °C
          Ambient operating temperature at V N
          Storage temperature                          -40 °C ... +70 °C
          Dimensions (mm) W x H x L                     17.5 x 55 x 90
                                                 Height from upper-edge of DIN 35 rail
          Wire connection                               CAGE CLAMP ®
          Cross sections                         0.08 mm² … 2.5 mm² / AWG 28 … 14
          Strip length                               5 … 6 mm / 0.2 … 0.24 in
          Standards/specifications                  EN 60664-1, EN 61810-1,
                                                      EN 61140, EN 50178