Page 108 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 108

1    Relay Modules in DIN-Rail Mount Enclosure



  106
                                            Relay with 2 break and 2 make contacts (2 ar) Relay with 2 break and 2 make contacts ( 2 ar)
                                            Nominal input voltage V            Nominal input voltage V
                                                                                                N
                                                             N
                                            24 V DC                            12 V, 24 V AC/DC



            Contact voltage (V)  1000   DC resistive load AC resistive load



              100


              10


                                  0.1           1                 10
                          Contact current (A)
        Load limit curve

                                                                                                14 24 12 22
                                                            14 24 12 22
                                                    A1                                 A1
                                                     +                                   ~
        Note:Inductive loads have to be attenuated by an                               A2
                                                    A2                                   ~
        appropriate protective circuit in order to protect relay coils    –
                                                    A2                                 A2
        and contacts!                                –      13 23 11 21                  ~      13 23 11 21
        Description                                           Item No.   Pack.                   Item No.   Pack.
                                            V N
                                                                         Unit  V N        I N               Unit
                                                       I N
        Relay module in DIN-rail mount enclosure,   24 V DC  12 mA  789-336  1  12 V AC/DC  21 mA  789-535  1
        for DIN 35 rail                                                        24 V AC/DC  12 mA  789-536   1




        Technical Data                              Accessories see pages 115           Accessories see pages 115

        Coil:
          Input voltage range                          V N  -15 % ... +10 %               V N  -15 % ... +10 %
        Contacts:
          Contact material                               AgNi + Au                          AgNi + Au
          Max. continuous current                          4 A                                4 A
          Max. make current                                 -                                  -
          Max. switching voltage                          250 VAC                            250 VAC
          Max. switching power (resistive)      1 kVA / 90 W, resistive see load limit curve  1 kVA / 90 W, resistive see load limit curve
          Recommended minimum load                    12 V AC/DC, 100 mA                 12 V AC/DC, 100 mA
          Pull-in/drop-out/bounce time typ.           15ms / 10ms / 1 ms                 20ms / 20ms / 1 ms
        General specifications:
          Nominal voltage to EN 60664-1                230 V / 2.5 kV / 2                 230 V / 2.5 kV / 2
          Dielectric strength, contact-coil (AC, 1 min)   1.5 kV rms                         1.5 kV rms
          Dielectric strength open contact (AC, 1 min)   0.75 kV rms                        0.75 kV rms
          Dielectric strength contact-contact (AC, 1 min)  1 kV eff                           1 kV eff
                                                       -25 °C ... +40 °C                  -25 °C ... +40 °C
          Ambient operating temperature at V N
          Storage temperature                          -40 °C ... +85 °C                  -40 °C ... +85 °C
          Dimensions (mm) W x H x L                     17.5 x 55 x 90                     17.5 x 55 x 90
                                                 Height from upper-edge of DIN 35 rail  Height from upper-edge of DIN 35 rail
          Wire connection                               CAGE CLAMP ®                       CAGE CLAMP ®
          Cross sections                         0.08 mm² … 2.5 mm² / AWG 28 … 14   0.08 mm² … 2.5 mm² / AWG 28 … 14
          Strip length                               5 … 6 mm / 0.2 … 0.24 in           5 … 6 mm / 0.2 … 0.24 in
          Standards/specifications                  EN 60664-1, EN 61810-1              EN 60664-1, EN 61810-1
   103   104   105   106   107   108   109   110   111   112   113