Page 109 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 109

1



                                                                                                                    107
                                              Relay with 1 changeover contact (1 u),   Relay with 2 changeover contacts (2 u),
                                              manual configuration,              manual configuration,
                                              electrical and mechanical activation indicator  electrical and mechanical activation indicator  1




             Switching current (A)  AC resistive load






                  DC resistive load



                            Switching voltage (V)
           Load limit curve for 788-346, -347, -349, -391  Similiar to picture   Similiar to picture

                                                                                                       14
                                                                    14
                                                                                                       12
                                                      A1            12                   A1            24
                                                       +                                  +            22
           Note: Inductive loads have to be attenuated by an
                                                      A2                                 A2
           appropriate protective circuit in order to protect relay coils    –            –            21
           and contacts.                                            11                                 11
           Description                                          Item No.   Pack.                   Item No.   Pack.
                                                         I N
                                                                           Unit  V N        I N               Unit
                                              V N
           Relay module in DIN-rail mount enclosure,   24 VDC  17 mA  789-1341  1  24 VDC   17 mA  789-1346   1
           for DIN 35 rail





           Technical Data                              Accessories see pages 115          Accessories see pages 115

           Coil:                                                                                                    8
            Input voltage range                          U N  -10% ... +10 %                U N  -10% ... +10 %
           Contacts:
            Contact material                                 AgNi                               AgNi
            Max. continuous current                          12 A                                8 A
            Max. make current                                16 A                                8 A
            Max. switching voltage                          250 VAC                            250 VAC
            Max. switching power (resistive)               3000 VA AC                        2 x 2000 VA AC
            Pull-in/drop-out/bounce time typ.             15ms / 8ms / -                     15ms / 8ms / -
                                                          6
                                                                                             6
            Mechanical life                           5 x 10  switching operations       5 x 10  switching operations
           General specifications:
            Nominal voltage to EN 60664-1                 250V / 4kV / 3                     250V / 4kV / 3
            Dielectric strength, contact-coil (AC, 1 min)   3.5 kV rms                         3.5 kV rms
            Dielectric strength open contact (AC, 1 min)     1 kV rms                           1 kV rms
            Dielectric strength contact-contact (AC, 1 min)   -                                1.5 kV eff
                                                         -25 °C ... +50 °C                  -25 °C ... +50 °C
            Ambient operating temperature at V N
            Storage temperature                          -40 °C ... +70 °C                  -40 °C ... +70 °C
            Dimensions (mm) W x H x L                     17.5 x 55 x 90                     17.5 x 55 x 90
                                                   Height from upper-edge of DIN 35 rail  Height from upper-edge of DIN 35 rail
            Wire connection                               CAGE CLAMP ®                       CAGE CLAMP ®
            Cross sections                         0.08 mm² … 2.5 mm² / AWG 28 … 14   0.08 mm² … 2.5 mm² / AWG 28 … 14
            Strip length                               5 … 6 mm / 0.2 … 0.24 in           5 … 6 mm / 0.2 … 0.24 in
            Standards/specifications                       EN 60664-1                         EN 60664-1
   104   105   106   107   108   109   110   111   112   113   114