Page 479 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 479

Pluggable Modules on Terminal Blocks - Surge Suppression Devices                                        10


                                                                                                                    477
                                              Single stage suppression for 3-wire control,   Single stage suppression for 3-wire control,
                                              signal or power circuits           signal or power circuits
                                              No interruption of current flow when   No interruption of current flow when
                                              changing module 24 V AC/DC         changing module 110 V / 120 V AC; 230 V AC
                                              Module width 15 mm / 0.591 in      Module width 15 mm / 0.591 in


           Note:
           For isolation measurements the ground (earth) contact at
           the transient suppression module must be disconnected.

           WSB marker card
           • Marking F; Item No.: 209-791
           • Marking 1 ... 10; Item No.: 209-702
           • Marking Lin, N, PE Lout, N, PE, Lin, N, PE;
            Item No.: 249-655
           5 cards, each containing 10 strips with 10 markers




                                              L IN                         L OUT  L IN                        L OUT

                                              N                            N     N                            N


                                              PE                           PE    PE                           PE
           Description                                     Item No.        Pack.               Item No.       Pack.
                                              V BN
                                                                           Unit  V BN                         Unit
           Surge suppression module           24 V AC/DC   286-836         1     230  V  AC    286-835        1
                                                                                 115 V AC      286-835/115-000  1









           Technical Data                            Accessories see pages 99 … 100     Accessories see pages 99 … 100
                                                           24 V AC/DC                      230 V AC; 115 V AC
           Nominal operating voltage V BN
           Operating voltage                             35 V AC / 45 V DC                 275 V AC; 150 V AC
           Nominal current                                   10 A                               10 A
           Nominal discharge current between L/N and PE      300 A                              1 kA
           Nominal discharge current between L and N         300 A                              1 kA
           Max. surge current between L/N and PE             1 kA                               4.5 kA
           Max. surge current between L and N                1 kA                               4.5 kA
           Protection level between L/N and PE               700 V                            1,3 kV; 1 kV
           Protection level between L and N                  100 V                            700 V; 400 V
           Response time between L/N and PE                  1 μs                               1 μs
           Response time between L and N                     25 ns                              25 ns              10
           Nominal voltage to EN 60664-1                 250 V / 4 kV / 2                    250 V / 4 kV / 2
           Ambient operating temperature                 -25 °C ... +85 °C                  -25 °C ... +85 °C
           Dimensions (mm) L x H x W incl. terminal block  17 x 82.5 x 73                    17 x 82.5 x 73