Pluggable Modules for Terminal Blocks - Surge Suppression Devices                                       10


                                                                                                                    479
                                              Three-stage suppression for 2-wire data,   Three-stage suppression for 3-wire data,
                                              measuring and control circuits 24 V DC   measuring and control circuits 12 V DC



                                              Module width 20 mm / 0.787 in      Module width 20 mm / 0.787 in
















           Note:
           For isolation measurements the ground (earth) contact at the
           transient suppression module must be disconnected.
           WSB marker card                    +                             +    L IN                         L OUT
           • Marking F; Item No.: 209-791
           • Marking 1 ... 10; Item No.: 209-702
           • Marking +/-; Item No.: 209-652   U                                  PE                           PE
                                               B
           • Marking Lin, PE, PE, N, Lout, PE, PE, N;
            Item No.: 249-652
           5 cards, each containing 10 strips with 10 markers  –            –    N                            N
           Description                                     Item No.        Pack.               Item No.       Pack.
                                              V BN
                                                                           Unit  V BN                         Unit
           Surge suppression module           24 V DC      286-833         1     12  V  DC     286-834        1










           Technical Data                            Accessories see pages 99 … 100     Accessories see pages 99 … 100
                                                            24 V DC                            12 V DC
           Nominal operating voltage V BN
           Operating voltage                                30 V DC                            14 V DC
           Nominal current                                   0.1 A                               6 A
           Nominal discharge current between L/N and PE                                         1.5 kA
           Nominal discharge current between L and N         5 kA
           Max. surge current between L/N and PE                                                1.5 kA
           Max. surge current between L and N                5 kA
           Protection level between L/N and PE                                                  ≤ 22 V
           Protection level between L and N                 ≤ 59 V
           Response time between L/N and PE                                                    ≤ 10 ns
           Response time between L and N                    ≤ 10 ns                                                10
           Through resistance / inductivity              20 mΩ / 2 x 7 μH                    50 mΩ / 14 μH
           Ambient operating temperature                 -25 °C ... +85 °C                  -25 °C ... +85 °C








           Accessories                                     Item No.        Pack.               Item No.       Pack.
                                                                           Unit                               Unit
           Terminal block for pluggable modules, with 2-
           conductor terminal blocks, orange separator ➊  22 mm / 0.866 in   280-638  1  22 mm / 0.866 in   280-638  1
           with 4-conductor terminal blocks, orange separator ➋  22 mm / 0.866 in   280-628  1  22 mm / 0.866 in   280-628  1
           with 4-conductor terminal blocks, marker plate ➋   25 mm / 0.984 in   280-764  1  25 mm / 0.984 in   280-764  1
           wire range 0.08 mm² ... 2.5 mm² / AWG 28 ... 14;
           stripped length 8 ... 9 mm / 0.33 in