                                                                                                                    95
                                              Off-delay timing with trigger voltage 1   Off-delay timing with trigger voltage 1
                                              changeover contact specified time   changeover contact specified time
                                              acc. to IEC 255, part 1            acc. to IEC 255, part 1            1
                                              Module width 20 mm / 0.787 in      Module width 20 mm / 0.787 in




              U
                         U
                          B
                              U
                               R
                         t
                         v
                                         t
              U
                       U
                        St

                                         t
           V B  = operating voltage; V St  = control voltage; V R  = voltage on relay;
           t V  = delay time
           Off-delay time relay with auxiliary voltage
           V B  on A1+ and A2- applied: relay stays in rest position;   A1  12           A1            12
                                                       +                                  ~
           V St  on St+ applied: relay switches to working condition   A1                A1
           V St  interrupted: t V  is activated; t V  is over: relay switches off   +  11  ~           11
           WSB marker cards                           St                                  St
                                                       +                                  ~
           • Marking K; Item No.: 209-782
                                                                    11                                 11
           • Marking 1 ... 10; Item No.: 209-702
           • Marking A1, A1, St, A2, A2, 12, 11, 11, 14;   A2       14                   A2            14
                                                       –                                  ~
            Item No.: 209-601
           Description                        Time range   Item No.        Pack.   Time range  Item No.       Pack.
                                                                           Unit                               Unit
           Time relay module                  0.1 - 1 s    286-440         1     0.1 -  1  s   286-446        1
                                              1 - 10 s     286-442         1     1 - 10 s      286-448        1
                                              10 - 100 s   286-444         1     10 - 100 s    286-450        1



           Technical Data                            Accessories see pages 99 … 100     Accessories see pages 99 … 100

           Nominal input voltage (V N )                     24 V DC                            230 V AC             8
           Current input at rated voltage (coil 20 °C)      16,0 mA                            16,8 mA
           Contact material                                 Ag.-Leg.                           Ag.-Leg.
           Max. switching voltage                       250 V DC / 250 V AC                250 V DC / 250 V AC
           Max. make current                                 26 A                               26 A
           Max. continuous current                           5 A                                 5 A
           Max. switching power (resistive)                 1250 VA                            1250 VA
           Pull-in/drop-out/bounce time typ.             15ms / 0ms / 2 ms                  15ms / 0ms / 2 ms
           Trigger voltage                                  24 V DC                            230 V AC
           Reset time                                        15 ms                              15 ms
           Repeat accuracy                                  ±0.5 %                              ±0.5 %
           Dielectric strength contact-coil (AC, 1 min)      2 kV                               2 kV
           Nominal voltage acc. to VDE 0110 Part 1/4.97,   250 V / 4 kV / 2                 250 V / 2,5 kV / 2
           IEC 60664-1
                                                                                             7
                                                          7
           Mechanical life                            5 x 10  switching operations       5 x 10  switching operations
                                                          5
                                                                                             5
           Mechanical life at max. load (resistance)  1 x 10  switching operations       1 x 10  switching operations
           Ambient operating temperature                 -25 °C ... +40 °C                  -25 °C ... +40 °C
           Dimensions (mm) L x H x W incl. terminal block  20 x 82.5 x 50                    20 x 82.5 x 50




           Accessories                                     Item No.        Pack.               Item No.       Pack.
                                                                           Unit                               Unit
           Terminal block for pluggable modules, with 2-
           conductor terminal blocks, orange separator ➊  22 mm / 0.866 in wide  280-638  1  22 mm / 0.866 in wide  280-638  1
           with 4-conductor terminal blocks, orange separator ➋  22 mm / 0.866 in wide  280-628  1  22 mm / 0.866 in wide  280-628  1
           with 4-conductor terminal blocks, marker plate ➋   25 mm / 0.984 in wide  280-764  1  25 mm / 0.984 in wide  280-764  1
           wire range 0.08 mm² ... 2.5 mm² / AWG 28 ... 14;
           stripped length 8 ... 9 mm / 0.33 in