Page 95 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 95

Pluggable Modules - Time Relays                                                                         1


                                                                                                                    93
                                              On-delay timing 1 changeover contact   On-delay timing 1 changeover contact
                                              specified time acc. to IEC 255, part 1   specified time acc. to IEC 255, part 1
                                              Module width 20 mm / 0.787 in      Module width 20 mm / 0.787 in      1









              U
                        U
                        B
                                U
                                 R
                t
                v
                                         t
           V B  = operating voltage; V St  = control voltage; V R  = voltage on relay;
           t V  = delay time
           On-delay time relay                        A1            12                   A1            12
           V B  on A1+ and A2- applied: relay stays in rest position   +                  ~
                                                                                         A1
                                                      A1
           delay time t V  is over: relay switches to working condition   +  11           ~            11
           WSB marker cards
           • Marking K; Item No.: 209-782
           • Marking 1 ... 10; Item No.: 209-702      A2            11                   A2            11
           • Marking A1, A1, A2, A2, 12, 11, 11, 14;    –                                 ~
            Item No.: 209-996                         A2            14                   A2            14
                                                       –
           5 cards, each containing 10 strips with 10 markers                             ~
           Description                        Time range   Item No.        Pack.   Time range  Item No.       Pack.
                                                                           Unit                               Unit
           Time relay module                  0.1 - 1 s    286-600         1     0.1 -  1  s   286-610        1
                                              1 - 10 s     286-602         1     1 - 10 s      286-612        1
                                              10 - 100 s   286-604         1     10 - 100 s    286-614        1





                                                                                                                    8
           Technical Data                            Accessories see pages 99 … 100     Accessories see pages 99 … 100
           Nominal input voltage (V N )                     24 V DC                            230 V AC
           Current input at rated voltage (coil 20 °C)      12,5 mA                            14,4 mA
           Contact material                                 AgCdO                              AgCdO
           Max. switching voltage                           380 V AC                           380 V AC
           Max. make current                                1 s 15 A                           1 s 15 A
           Max. continuous current                           6 A                                 6 A
           Max. switching power (resistive)                  2000 VA                           2000 VA
           Pull-in/drop-out/bounce time typ.            0 ms / 15 ms / 1 ms                 0 ms / 15 ms / 1 ms
           Reset time                                       100 ms                             100 ms
           Repeat accuracy                                  ±0.5 %                              ±0.5 %
           Dielectric strength contact-coil (AC, 1 min)      3 kV                               3 kV
           Nominal voltage acc. to VDE 0110 Part 1/4.97,   250 V / 4 kV / 2                  250 V / 4 kV / 2
           IEC 60664-1
                                                                                             7
                                                          7
           Mechanical life                            5 x 10  switching operations       5 x 10  switching operations
                                                          5
                                                                                             5
           Mechanical life at max. load (resistance)  1 x 10  switching operations       1 x 10  switching operations
           Ambient operating temperature                 -25 °C ... +40 °C                  -25 °C ... +40 °C
           Dimensions (mm) L x H x W incl. terminal block  20 x 82.5 x 50                    20 x 82.5 x 50



           Accessories                                     Item No.        Pack.               Item No.       Pack.
                                                                           Unit                               Unit
           Terminal block for pluggable modules, with 2-
           conductor terminal blocks, orange separator ➊  22 mm / 0.866 in wide  280-638  1  22 mm / 0.866 in wide  280-638  1
           with 4-conductor terminal blocks, orange separator ➋  22 mm / 0.866 in wide  280-628  1  22 mm / 0.866 in wide  280-628  1
           with 4-conductor terminal blocks, marker plate ➋   25 mm / 0.984 in wide  280-764  1  25 mm / 0.984 in wide  280-764  1
           wire range 0.08 mm² ... 2.5 mm² / AWG 28 ... 14;
           stripped length 8 ... 9 mm / 0.33 in
   90   91   92   93   94   95   96   97   98   99   100