          6.5	 Choosing	the	power	supply	unit	and	drive
      AFE200 • Active Front End Regenerative Power Supply Unit
          Design                                              •   Single-motor calculation based on motor output power

          AFE200 drives are normally used in applications that require   Mains:     Vmains = three-phase 400Vac
          the re-introduction of power into the mains. They can also be
      ADV200 - 4 • Basic
          used when regeneration is not required, to achieve unitary   Motor:     Poutm = 132kW
          cos phi or low total harmonic distortion values (which standard         Voutm = 400Vac
          inverters do not guarantee, even with a DC or line choke).         ηm = 0.95;
          This section provides some examples of design, from the sim-        Im = 236A
          plest, single-motor configuration to more complex ones.
          As a general rule, the AFE2000 should be at least the same   Application:   Requires 100% of motor power
          size as the drive, which is usually an ADV200-DC.                 Requested overload = 150%
          In certain cases the size can be chosen according to the
          work cycles and load profiles of each drive, in both motor or
          generator mode.                                     > Calculation of the current required on the DC-link:
          Another calculation to be performed is the sum of the loads
          connected to the DC-LINK, obtained from the total of the
          parallel connections.                                IDc =    Poutm [KW]     132 * 1000  = 220 A
          The sum of the loads of each drive must be less than the    VDclinK * ηm * ηD  650 * 0.95 * 0.97
          maximum value specified in the AFE200 user guide in order to
          guarantee correct pre-load circuit operation.
          Precharge kit must be selected according to AFE size and the   > Choosing the power supply unit:
          capacity connected to the DC-Link (see AFE manual, chapter
          "5.5 Precharge Kit").                               The AFE200 must be capable of delivering a current of ≥ 220 A
          LCL Filter must be selected considering the use of the AFE:   Choose the size with the appropriate characteristics from the
          Heavy Duty or Low Duty overload (see AFE manual chapter   catalogue (section AFE200  "2.7 Output Data" on page 39):
          "5.6 LCL Filters").                                 AFE200-61320.

          Key to symbols
                                                              > Choosing the drive:
          Poutm   Motor output power (continuous operation)
          Voutm   Motor rated voltage                         Choose the size with the rated current required by the motor
          Vmains   Rated voltage of the AC power supply
          Poutd   Drive output power (light or heavy overload)   (≥ 236A) from the catalogue  (section ADV200-DC "2.7 Output
          ηm     Typical motor efficiency                     Data" on page 39):
          ηd     Typical drive efficiency (0.97)              With a 650 Vdc drive:
          Pdc    Power requested by the DC - Link
          Im     Motor rated current                          ADV-71600-...-DC (In = 270A, OK).
          Vdclink   DC-link rated voltage
                 650Vcc at 400Vac                              Drive               Description     Code     Q.ty
                 750Vcc at 460Vac
                 930Vcc at 575Vac                              ADV200-DC           ADV-71600-KXX-4-DC  S9020DC  1
                 1120Vcc at 690Vac
                                                               AFE + components    Description     Code
                                                               AFE regenerative    AFE200-61320-KXX-4  S9AF04  1
          Note!    For special applications please contact techno-  Pre-charge kit  PRE CHARGE KIT-  S728281  1
                  help@gefran.com.                                                 AFE-90/132-4
                                                               Kit LCL (required Heavy Duty   LCL-Kit-AFE-4-132-HD  S7LC03  1
                                                               overload)
                                                               EMI filter          EMI FN3120 -480V-230A  S74EE  1
                                                               Fuses mains side connection   S1üf1/110/315A/690V  F4G30  3




                                                              Checking total DC-link capacity:
                                                              AFE200-61320 with ADV-71600-...-4-DC = 13600 + 16800 =
                                                              30400 μF ≤ 43000 μF (OK). See table on page 104