Page 103 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 103
Gefran Spa - Drive & Motion Control Unit • www.gefran.com 103
AC Input current for continuous Switching frequency Reduction factor
operation In fsw
Sizes Kf Kalt ADV200 - 4
AFE200-..-4 HD LD Default Higher Kv Kt (@ 8 kHz) %
@400 Vac @400 Vac (1) (2) (3) (4)
[A] [A]
3220 40 60 8 - 0.9 - 1.2
4450 80 100 8 - 0.9 - 1.2 ADV200-DC
5900 160 200 4 6.8 0.9 0,7 1.2
61320 230 280 4 6.8 0.9 0,7 1.2
71600 280 340 4 - 0.9 - 1.2
72000 340 400 2 4 0.9 - 1.2
72500 400 500 2 4 0.9 - 1.2
HD: 0.9 ADV200 - 6
73150 500 560 2 - 0.9 - 1.2
LD: 0.8
73550 560 600 2 - 0.9 - 1.2
400 kW 600 760 2 - 0.9 - 1.2
500 kW 760 950 2 - 0.9 - 1.2
630 kW 950 1060 2 - 0.9 - 1.2 ADV100
710 kW 1060 1050 2 - 0.9 - 1.2
900 kW 1400 1500 2 - 0.9 - 1.2
1 MW 1500 1730 2 - 0.9 - 1.2
ADV80
AC Input current for continuous Switching frequency Reduction factor
operation In fsw
Sizes Kv
AFE200-..-6 HD LD Default Higher Kt Kalt
%
(7)
@690 Vac @690 Vac (6) HD LD (4) AFE200
[A] [A]
71600 150 190 4 - 1 1.2
72000 190 240 2 - 1 1.2
0.9 0.8
72500 240 300 2 - 1 1.2
73150 300 340 2 - 1 1.2 FFE200
73550 340 (5) 380 2 - 1 0.85 0.8 1.2
400 kW 360 455 2 - 1 1.2
500 kW 455 570 2 - 1 0.9 0.8 1.2
630 kW 570 645 2 - 1 1.2
710 kW 645 (5) 720 2 - 1 0.85 0.8 1.2 SMB200
900 kW 850 920 2 - 1 0.9 0.8 1.2
1 MW 920 (5) 1150 2 - 1 0.85 0.8 1.2
1.35 MW 1200 (1) 1350 2 - 1 0.85 0.8 1.2
1.65 MW 1470 (1) 1645 2 - 1 0.85 0.8 1.2
HD: Heavy Duty (150% overload) PROGRAM.
LD: Light Duty (110% overload)
(1) Kv : Derating factor for mains voltage at 460Vac
(2) Kt : Derating factor for ambient temperature of 50°C (1% every °C over 40°C with HD and 2% every °C over 40°C with LD)
(3) Kf : Derating factor for higher switching frequency
(4) Kalt : Derating factor for installation at altitudes above 1000 meters a.s.l. Value to be applied = 1.2% each 100 m increase above 1000 m.
For example: Altitude 2000 m, Kalt = 1.2% * 10 = 12% derating; In derated = (100 - 12) % = 88 % In
(5) Current values with an ambient temperature of 35°C.
(6) Kv : Derating factor for DC power supply (690 V)
(7) Kt : Derating factor for ambient temperature of 50°C (1% every °C over 40°C with HD and 2% every °C over 40°C with LD)
For sizes 73550, 710 kW and1000 kW: Derating factor for ambient temperatures of > 40°C up to 50°C (1% every °C over 35°C with HD and 2% every °C over 40°C with LD) APPENDIX