                      AC Input current for continuous   Switching frequency             Reduction factor
                              operation In                    fsw
             Sizes                                                                                Kf     Kalt       ADV200 - 4
           AFE200-..-4     HD            LD          Default        Higher       Kv      Kt     (@ 8 kHz)  %
                         @400 Vac      @400 Vac                                  (1)     (2)      (3)     (4)
                           [A]           [A]
           3220            40             60            8             -          0.9               -      1.2
           4450            80            100            8             -          0.9               -      1.2       ADV200-DC
           5900            160           200            4             6.8        0.9              0,7     1.2
           61320           230           280            4             6.8        0.9              0,7     1.2
           71600           280           340            4             -          0.9               -      1.2
           72000           340           400            2             4          0.9               -      1.2
           72500           400           500            2             4          0.9               -      1.2
                                                                                        HD: 0.9                     ADV200 - 6
           73150           500           560            2             -          0.9               -      1.2
                                                                                        LD: 0.8
           73550           560           600            2             -          0.9               -      1.2
           400 kW          600           760            2             -          0.9               -      1.2
           500 kW          760           950            2             -          0.9               -      1.2
           630 kW          950           1060           2             -          0.9               -      1.2       ADV100
           710 kW          1060          1050           2             -          0.9               -      1.2
           900 kW          1400          1500           2             -          0.9               -      1.2
           1 MW            1500          1730           2             -          0.9               -      1.2
                                                                                                                    ADV80


                      AC Input current for continuous   Switching frequency             Reduction factor
                              operation In                    fsw
             Sizes                                                                Kv
           AFE200-..-6     HD            LD          Default        Higher                    Kt        Kalt
                                                                                                         %
                                                                                              (7)
                         @690 Vac      @690 Vac                                   (6)      HD    LD      (4)        AFE200
                           [A]           [A]
           71600           150           190            4             -            1                     1.2
           72000           190           240            2             -            1                     1.2
                                                                                           0.9   0.8
           72500           240           300            2             -            1                     1.2
           73150           300           340            2             -            1                     1.2        FFE200
           73550          340 (5)        380            2             -            1       0.85  0.8     1.2
           400 kW          360           455            2             -            1                     1.2
           500 kW          455           570            2             -            1       0.9   0.8     1.2
           630 kW          570           645            2             -            1                     1.2
           710 kW         645 (5)        720            2             -            1       0.85   0.8    1.2        SMB200
           900 kW          850           920            2             -            1       0.9   0.8     1.2
           1 MW           920 (5)        1150           2             -            1       0.85  0.8     1.2
           1.35 MW        1200 (1)       1350           2             -            1       0.85  0.8     1.2
           1.65 MW        1470 (1)       1645           2             -            1       0.85  0.8     1.2

          HD: Heavy Duty (150% overload)                                                                            PROGRAM.
          LD: Light Duty (110% overload)
          (1) Kv :    Derating factor for mains voltage at 460Vac
          (2) Kt :    Derating factor for ambient temperature of 50°C (1% every °C over 40°C with HD and 2% every °C over 40°C with LD)
          (3) Kf :    Derating factor for higher switching frequency
          (4) Kalt :    Derating factor for installation at altitudes above 1000 meters a.s.l. Value to be applied = 1.2% each 100 m increase above 1000 m.
                 For example: Altitude 2000 m, Kalt = 1.2% * 10 = 12% derating; In derated = (100 - 12) % = 88 % In
          (5)     Current values with an ambient temperature of 35°C.
          (6) Kv :    Derating factor for DC power supply (690 V)
          (7) Kt :   Derating factor for ambient temperature of 50°C (1% every °C over 40°C with HD and 2% every °C over 40°C with LD)
                 For sizes 73550, 710 kW and1000 kW: Derating factor for ambient temperatures of > 40°C up to 50°C (1% every °C over 35°C with HD and 2% every °C over 40°C with LD)  APPENDIX