Page 102 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 102

102                                Inverter System & Power Supply Unit





          6.6	 Input	Data
      AFE200 • Active Front End Regenerative Power Supply Unit
                           Input voltage       Overvoltage threshold   Undervoltage threshold  Input    Cosphi
            Sizes             Uln                  (Overvoltage)           (Undervoltage)   current THD
            AFE200   AFE200-...-4/4A  AFE200-... -6/6A  AFE200-...-4/4A  AFE200-... -6/6A  AFE200-...-4/4A  AFE200-... -6/6A
      ADV200 - 4 • Basic
                        [Vac]       [Vac]       [Vdc]       [Vdc]       [Vdc]       [Vdc]
           3220
           4450
                                      -                                              -
           5900
           61320
           71600
           72000
           72500     380 - 15% ... 500                                                         ≤ 3%
                                                                       380 Vdc
           73150       Vac +5%                 820 Vdc                (@ 400 Vca)            (Considering
                      50/60 Hz ±2%                                                           a network
           73550                 500 - 10% ... 690         1192 Vdc                          with voltage   ≥ 0.99
                                                                                   676 Vdc
           400 kW                  Vac +10%                                       (@ 690 Vac)  THD of less
                                 50/60 Hz ±2%                                                 than 2%).
           500 kW
                                                                                   563 Vdc
           630 kW                                                                 (@ 575 Vac)
           710 kW
           900 kW
           1 MW
           1.35 MW        -                       -                      -
           1.65 MW        -                       -                      -



                                                     Input current THD
                         “Clean Power” Technology. The AFE200 integrates cutting-edge energy recovery and energy efficiency technology.














                        From AC inverter                                          From AFE200 power supply unit





                                                  Mains input power factor
                              The AFE200 uses advanced control algorithms to maintain the input current in phase with voltage.











                                                  _____
                                                        Mains voltage
                                                  _____
                                                        Mains current
                        From AC inverter                                          From AFE200 power supply unit
   97   98   99   100   101   102   103   104   105   106   107