Page 120 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 120

120                                Inverter System & Power Supply Unit






                       AC Input current for continuous             Reduction factor              DC Link Capacity
      FFE200 • Fundamental Front End Regenerative Power Supply Unit
                               operation In
             Sizes
           FFE200-4        HD             LD              Kt            Kalt            Kv            Total
                         @400 Vca       @400 Vca          (1)            (2)            (3)            [µF]
                          [Arms]         [Arms]
      ADV200 - 4 • Basic
           FFE200-550-4     465            552                                                        16800
           FFE200-730-4     619            724                                                        20400
           FFE200-880-4     746            890                                                        25200
           2x550            860           1021                                                       2 x 16800
           2x730           1145           1339                                                       2 x 20400
           2x880           1379           1647                                                       2 x 25200
                                                          1.2            1 %          See figure
           3x730           1717           2008                                                       3 x 20400
           3x880           2069           2470                                                       3 x 25200
           4x730           2290           2677                                                       4 x 20400
           4x880           2758           3294                                                       4 x 25200
           5x730           2862           3347                                                       5 x 20400
           5x880           3448           4117                                                       5 x 25200


                       AC Input current for continuous             Reduction factor              DC Link Capacity
                               operation In
             Sizes
           FFE200-6        HD             LD              Kt            Kalt            Kv            Total
                         @690 Vca       @690 Vca          (1)            (2)            (3)            [µF]
                          [Arms]         [Arms]
           FFE200-500-6     430            492                                                        11200
           FFE200-690-6     582            682                                                        13600
           FFE200-760-6     639            744                                                        13600
           2x500            795            910                                                       2 x 11200
           2x690           1077           1262                                                       2 x 13600
           2x760           1182           1377                                                       2 x 13600
                                                          1.2            1 %          See figure
           3x690           1616           1894                                                       3 x 13600
           3x760           1772           2065                                                       3 x 13600
           3x690           2155           2525                                                       4 x 13600
           4x760           2363           2754                                                       4 x 13600
           5x690           2693           3156                                                       5 x 13600
           5x760           2954           3442                                                       5 x 13600



          HD: Heavy Duty (150% overload for 60 seconds every 300 seconds)
          LD: Light Duty (110% overload for 60 seconds every 300 seconds)
          (1) Kt :    Derating factor for room temperature > 40°C up to 50°C (1.2% each °C higher than 40°C).
                 You can also set parameter IPA564 (default=40) to 50 to obtain automatic derating of 0.9.
          (2) Kalt :    Derating factor for installation at altitudes above 2000 meters a.s.l. Value to be applied = 1% each 100 m increase above 2000 m. (up to a maximum of 4000 m).
                 For example: Altitude 3000 m, Kalt = 1% * 10 = 10% derating; In derated = (100 - 10) % = 90 % In
          (3) Kv   Supply voltage derating should also be taken into consideration for installations over 2000 m above sea level (to ensure isolation). See figure below.

                                   Derating  Kv  1.0

                                    0.9


                                    0.8


                                    0.7
                                      0          1000        2000        3000       4000
                                                                  Installation Altitude a.s.l. (meters)