AC Input current for continuous Reduction factor DC Link Capacity
FFE200 • Fundamental Front End Regenerative Power Supply Unit
operation In
Sizes
FFE200-4 HD LD Kt Kalt Kv Total
@400 Vca @400 Vca (1) (2) (3) [µF]
[Arms] [Arms]
ADV200 - 4 • Basic
FFE200-550-4 465 552 16800
FFE200-730-4 619 724 20400
FFE200-880-4 746 890 25200
2x550 860 1021 2 x 16800
2x730 1145 1339 2 x 20400
2x880 1379 1647 2 x 25200
1.2 1 % See figure
3x730 1717 2008 3 x 20400
3x880 2069 2470 3 x 25200
4x730 2290 2677 4 x 20400
4x880 2758 3294 4 x 25200
5x730 2862 3347 5 x 20400
5x880 3448 4117 5 x 25200
AC Input current for continuous Reduction factor DC Link Capacity
operation In
Sizes
FFE200-6 HD LD Kt Kalt Kv Total
@690 Vca @690 Vca (1) (2) (3) [µF]
[Arms] [Arms]
FFE200-500-6 430 492 11200
FFE200-690-6 582 682 13600
FFE200-760-6 639 744 13600
2x500 795 910 2 x 11200
2x690 1077 1262 2 x 13600
2x760 1182 1377 2 x 13600
1.2 1 % See figure
3x690 1616 1894 3 x 13600
3x760 1772 2065 3 x 13600
3x690 2155 2525 4 x 13600
4x760 2363 2754 4 x 13600
5x690 2693 3156 5 x 13600
5x760 2954 3442 5 x 13600
HD: Heavy Duty (150% overload for 60 seconds every 300 seconds)
LD: Light Duty (110% overload for 60 seconds every 300 seconds)
(1) Kt : Derating factor for room temperature > 40°C up to 50°C (1.2% each °C higher than 40°C).
You can also set parameter IPA564 (default=40) to 50 to obtain automatic derating of 0.9.
(2) Kalt : Derating factor for installation at altitudes above 2000 meters a.s.l. Value to be applied = 1% each 100 m increase above 2000 m. (up to a maximum of 4000 m).
For example: Altitude 3000 m, Kalt = 1% * 10 = 10% derating; In derated = (100 - 10) % = 90 % In
(3) Kv Supply voltage derating should also be taken into consideration for installations over 2000 m above sea level (to ensure isolation). See figure below.
Derating Kv 1.0
0.9
0.8
0.7
0 1000 2000 3000 4000
Installation Altitude a.s.l. (meters)