Page 116 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 116

116                                Inverter System & Power Supply Unit





          7.5	 Choosing	the	power	supply	unit	and	drive
      FFE200 • Fundamental Front End Regenerative Power Supply Unit
          Design                                              1. Single-motor applications

          FFE200 drives are used in applications that require the re-  3ph 400Vac          3ph 400Vac
          introduction of power into the mains.                       50Hz                  50Hz
      ADV200 - 4 • Basic
          This section provides some examples of design:
          1. Single-motor applications
          2. Multi-motor applications                                         LR3-4-PRC   LR3-4-FFE-550
          3. Multi-motor applications where regenerated power is a
           small percentage of motor power.
                                                                                               AC/DC Regen
                                                                                             FFE200-550-4+PRC
                                                                               DC
          Key to symbols                                                     Precharge
                                                                                           522Adc + ovld 150%
          Vmains   Rated voltage of the AC power supply                                       @ 540Vdc
          Poutm    Motor output power (continuous operation)
          Voutm   Motor voltage rating                                                       ADV200-72500
          ηm     Typical motor efficiency                                                     -KXX-4-DC
          ηd     Typical drive efficiency (0.97)
          Pdc    Power requested by the DC - Link
          Vdc    DC-link rated voltage
          Idc    Current requested by the DC-link
                                                                                250KW
                                                                                400Vac  M
          Note!    For special applications please contact techno-
                  help@gefran.com.
                                                              The application requires 100% of motor and regenerating
                                                              power of a single asynchronous motor with 150% overload for
          DC-link voltage depends on mains voltage, and under nominal   60s every 300s.
          load conditions is about 1.3 times the AC supply voltage.
          Therefore, for a 400VAC three-phase mains under nominal   Vmains = three-phase 400[V]
          load conditions, the DC-link voltage is about       Poutm = 250[KW]
          400Vac * 1.35 =  540Vdc.                            Voutm = 400[V]
          The same calculation must be used for a 690Vac mains or   ηm = 0.95
          other supply.
                                                              > Calculation of the current required on the DC-link:
                                                              Vdc=Vmains [V]* 1.35=400*1.35=540 [V]

                                                                               1000          1000
                                                               Pdc = Poutm [kW] *   =  250 *       = 271300 [W]
                                                                             (µm* µd)      0,95 * 0,97
                                                                     Pdc [W]   271300
                                                               Idc =        =         = 502 [A]
                                                                     Vdc [V]    540
                                                              > Choosing the power supply unit and accessories:
                                                              The chosen FFE200 power supply must be able to deliver cur-
                                                              rent ≥ 502[A] with 150% overload.
                                                              Choose the size with the appropriate voltage and current
                                                              characteristics from section "7.7 Output Data" on page 121 (see
                                                              column DC output current @ 380…500VAC – Heavy Duty):
                                                              no.1 FFE200-550-4+PRC

                                                              The added code +PRC indicates that the power supply has a
                                                              precharge circuit for the condenser bank on the DC-link.
                                                              Choose the mains inductance and the FFE precharge induct-
                                                              ance from section "10.2.1. Input choke (L1 - CA)" on page 148:
                                                              no.1 LR3-4-FFE-550
                                                              no.1 LR3-4-PRC