Page 607 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 607
“Alu-Plus” Contact Paste
14
605
Syringe
WAGO PUSH WIRE connectors
®
Push nozzle of the “Alu-Plus” syringe into the center con- Press plunger until “Alu-Plus” is visible in the other holes.
ductor entry hole of the WAGO PUSH WIRE connector.
®
Pack.
Item No.
Unit
Syringe,
contents: 20 ml “Alu-Plus” contact paste
249-130 20 (4x5)
WAGO lighting connectors
Push nozzle of the “Alu-Plus” syringe first into the circular Press plunger down until the “Alu-Plus” has filled both
and then into the square conductor entry hole of the holes.
WAGO lighting connector.
Termination of aluminum conductors
WAGO spring-clamp terminal blocks are suitable for solid
aluminum conductors 1 up to 4 mm²/AWG 12 if contact
paste “Alu-Plus” is used for the termination.
“Alu-Plus”
· Automatically destroys the oxide film during clamping
· Prevents fresh oxidation at the clamping point
· Prevents electrolytic corrosion between aluminum and
copper conductors (in the same connector)
· Offers permanent protection against corrosion
Using terminal blocks with CAGE CLAMP Spring Pressure
®
Connection Technology, aluminum conductors must first be WAGO rail-mount terminal blocks
cleaned and then immediately be inserted into the clamp- (only up to 4 mm²/AWG 12)
ing units filled with WAGO “Alu-Plus” contact paste. For each conductor entry: Insert nozzle of the “Alu-Plus” Press plunger down until “Alu-Plus” has filled each of these
syringe in every open conductor entry hole (one after the holes.
It is, of course, also possible to apply the “Alu-Plus” direct- other).
ly on the whole surface of the aluminum conductor before 1 Aluminum conductors in accordance with IEC 61545,
clamping. “Alu-Plus” in the syringe offers a higher degree of Class B, Alloy 1370, with a tensile strength of
security and cleanliness when terminating solid alu- 90 - 180 N/mm² and an elongation of 1 - 4%.
Please take into account that the nominal currents must be minum conductors. Filling is, for example, very Standard values: Tensile strength 90 - 180 MPa, elonga-
adapted to the reduced conductivity of the aluminum con- quickly performed on the three following selected tion 1 - 4% (acc. to EN 615.4.1)
ductors: connectors (see illustration).
2.5 mm²/AWG 14 = 16 A
4 mm²/AWG 12 = 22 A
14