            2.2    Commissioning of Escalators
                  2  No.  of  escalators  have  been  commissioned  by  conducting  all  types  of
                   prototype  tests  confirming  to  RDSO  latest  Spec  RDSO/PE/SPEC/TL/0095(Rev.’2’)-
                   2017  at  Circulating  area  towards  Platform  No.1  (New  FOB)  at  LPI  station  and
                   Circulating area (DN) at HYB station.











                                                Escalator at LPI Escalator at HYB
            2.3    Commissioning of 120 kVA UPS at PRS/SC:

                  2 sets of 2x60 KVA overaged & obsolete UPS system was successfully replaced with
                   2  sets  of  120  kVA  Modular  UPS  at  PRS/SC  which  are  feeding  the  vital  disaster
                   recovery  servers  of  Indian  Railways.  This  was  possible  because  of  meticulous
                   planning, coordination with CRIS team & execution by SSE/E/M/PRS’s Team under
                   the  guidelines  of  PCEE/SCR.  This  2  x120  kVA  UPS  has  better  redundancy  due  to
                   virtue  of  18  Modules  of  6.6  kVA  each  backed  up  by  2  exclusive  battery  banks
                   (either of them on standby). Each 120 kVA UPS can take full load of data center in
                   case of failure of any one of the UPS which was not possible in the earlier 2x60 kVA
                   single UPS unit.