Page 42 - GuardII+ Series 4208 Platform SM User Manual
P. 42

User Instructions



                        •  Each voltage and current input has a maximum Alert threshold set to 3x the average
                            data collected over the Auto-Learn period.
                        •  Each current input has a minimum Alert threshold set to 10% of the average data
                            collected over the Auto-Learn period.
                                     NOTE:
                                     The  maximum  Alert  thresholds  will  be  constrained  by  the  maximum
                                     sensitivity of the input.  For example, if average data collected over the
                                     Auto-Learn period for the TV input was 60 V then the calculated maximum
                                     Alert threshold would be 180 V.  However, if the TV input sensitivity is only
                                     80 V, then maximum Alert threshold is set to 80 V.

                                     NOTE:
                                     If the Auto-Learn process is interrupted by a power cycle, the monitor will
                                     start a new Auto-Learn when it is turned back on.

                                     NOTE:
                                     Once the Auto-Learn period is complete, use the ‘Synchronize’ function in
                                     IAM to import the new Alert thresholds into the database.

              6.3.5.  Upload Changes

                        Once the new settings have been selected, they need to be uploaded to the GuardII+.
                     This can be done directly using either an Ethernet or USB connection.













                                               Figure 6-20 IAM Upload Settings

                        •  Press the “Upload” button to upload the settings directly to the monitor.  This requires
                            a live Ethernet or USB connection to the GuardII+.  Once the settings are uploaded,
                            the monitor will reboot.
                                     NOTE:
                                     Until the new settings are uploaded into the GuardII+, it will continue to
                                     use the previous settings.